HVAC Guide Specifications
Heat Pump Air Cooled Liquid Chiller
Size Range:
5 Tons
Multiaqua Model Number:
MACH-060-1
Part 1 — General
1.01 SYSTEM DESCRIPTION
Multiaqua air cooled liquid heat pump chiller are designed using a scroll compressor, low sound condenser fans and a high
efficiency pump.
1.02 QUALITY ASSURANCE
A. Unit shall be certified in accordance with U.L. Standard 95, latest revision (U.S.A)
B. Construction shall comply with ASHRAE 15 Safety Code, NEC and ASME applicable codes (U.S.A. codes)
C. Manufactured in a facility registered to ISO 9002, Manufacturing Quality Standard.
D. ETL Certified.
E. Fully load run tested at the factory.
F. Damage resistant packaging.
1.03 DELIVERY, STORAGE AND HANDLING
A. Packaged and readied for shipment from the factory.
B. Unit controls shall be capable of withstanding 150F storage temperatures in the
control compartment.
C. Stored and handled per unit manufacturer’s recommendations.
1.04 WARRANTY
A. Complete unit, first year parts only warranty against manufacturer’s defects.
B. Compressor, years 2-5, parts only warranty against manufacturer’s defects.
Part 2 — Products
2.01 EQUIPMENT
A. General:
1. Factory-assembled, air cooled heat pump chiller.
2. Shall be assembled on heavy gauge steel mounting/lifting rails.
3. Contained within the unit cabinet shall be all factory wiring, piping controls, refrigerant
charge (R-407c), and special requirements prior to field start-up.
4. Brass body strainer with 20 mesh screen and blow down shall be supplied in cabinet as a
field installable accessory.
B. Unit
Cabinet:
1. Cabinet shall be galvanized steel casing with a baked polyester powder finish.
2. Cabinet shall be capable of withstanding 500-hour salt spray test in accordance with the ASTM
(U.S.A) standard.
C. Condenser
Fans:
1. 4-blade, condenser fans shall e direct-driven, aluminum construction, and shall be statically
and dynamically balanced with inherent corrosion protection.
2. Air shall be discharged horizontally.
3. Motors and fans shall be protected by coated steel wire safety guards.
D. Fan Motors:
1. Condenser fan motors shall be single speed, direct drive.
2. Totally enclosed.
3. Permanently lubricated sleeve bearings and Class F insulation.
4. Internal overload protection.
E. Compressors:
1. Fully hermetic scroll type compressor.
2. Direct Drive, 3500 rpm (50/60 Hz)
3. Compressor shall be suction gas cooled.
4. Internal motor protected.
5. Protected by high pressure and loss of charge devices.
6. External vibration isolation.