Wiring Connections for Three-Phase Scrolls
Scroll compressors will only compress gas in the clockwise direction when viewed from the
top. Since single-phase motors will start and run in only one direction, reverse rotation is not
a major consideration. Three-phase motors will start and run in either direction depending on
the phase angles of the supplied power. This requires care during installation to ensure the
compressor is operating in the proper direction. Verification of proper rotation is done by
observing suction and discharge pressures when the compressor is energized. Reverse
rotation is indicated by a decrease in discharge pressure and an increase in suction pressure.
Reverse rotation has no negative impact on the scroll compressors. However, after several
minutes of operation the compressor-line break will de-energize the compressor. In order to
correct this, disconnect power and switch any two power leads at the unit contactor. Never
switch leads directly at the compressor.