633 – SD P-ambient air (HDT2800)
-
Associated parameter 1.0700.087
Cause
Corrective action
Air humidity sensor defect.
u
Sensor is not currently part of standard scope of supply.
634 – SD T0-Ambient Air (HDT2800)
-
Associated parameter 1.0700.089
Cause
Corrective action
Air humidity sensor defect.
u
Sensor is not currently part of standard scope of supply.
635 – SD air humidity (HDT2800)
-
Associated parameter 1.0700.091
Cause
Corrective action
Air humidity sensor defect.
u
Sensor is not currently part of standard scope of supply.
642 – SD Electr. Motor Power AI2
Red alarm.
Associated parameter 2.8006.040
Cause
Corrective action
Motor power sensor defect
(analog input 2).
1. Effective generator power not transmitted correctly.
2. Effective generator power can be optionally transmitted by CAN
bus.
3. Check plant control application engineering.
646 – Al Knock Intensity
Red alarm.
Associated parameter 2.1200.934
Cause
Corrective action
Knock intensity exceeded
(extreme knocking detected).
1. Check gas quality if feasible (methane number).
2. Check emissions.
3. Check combustion chamber.
649 – Al Req Angle Throttle A
Yellow alarm.
Associated parameter 2.1200.935
Cause
Corrective action
Throttle A opening angle
exceeded.
1. Check charge pressure reserve.
2. Intake air temperature not as per TVU data.
3. Check compressor for contamination.
4. Reduce power.
MS15026/00E 2015-05
| Troubleshooting | 139
TIM-ID: 0000044567 - 003