48
Operation
3.2
Putting the engine into operation after scheduled
out-of-service-period
Preconditions
• Engine is stopped and starting disabled.
Putting the engine into operation
Item
Task
Lube oil system
Check oil level (
Cooling system
Check engine coolant level (
Check charge-air coolant level (
Cooling system
Preheat coolant with preheating unit.
Fuel prefilter
Drain (
Monitoring equipment
Carry out lamp test (see manufacturer’s documentation).
Engine/generator control system
Switch ON;
Select operating mode, e.g. MANUAL OPERATION,
AUTOMATIC OPERATION.
M015715/00E 06-08
© MTU
Содержание 20 V 4000 G23
Страница 9: ...04 Table of Contents M015715 00E 06 08 MTU...
Страница 19: ...14 Safety M015715 00E 06 08 MTU...
Страница 61: ...56 Operation M015715 00E 06 08 MTU...
Страница 73: ...68 Maintenance M015715 00E 06 08 MTU...
Страница 159: ...154 Task Description M015715 00E 06 08 MTU...
Страница 162: ...Special Tools 157 Part No Designation Use Qty F30510423 Torque wrench 10 60 Nm 1 F6784183 Puller 1 M015715 00E 06 08 MTU...
Страница 165: ...160 Special Tools M015715 00E 06 08 MTU...
Страница 166: ...Annex 161 8 Annex 8 1 Manufacturer s documentation See Manufacturer s documentation M015715 00E 06 08 MTU...
Страница 171: ...166 Annex M015715 00E 06 08 MTU...
Страница 175: ......
Страница 176: ...Demo version http www verypdf com...
Страница 177: ...Demo version http www verypdf com...
Страница 178: ...Demo version http www verypdf com...