7. Stack duct installation 

The stack outlet of the MTM 52 stove must be capped with the draught regulator (which is a part of 

the standard stove equipment) in the vertical position so that the exhaust fumes outlet is directed 

upwards. The stack must be installed into the exhaust fumes outlet of the draught regulator. 

To 

ensure 

proper 

combustion, 

the 

stack 

system 

must 

be 

installed 

properly. 

After the installation the following indications have to be followed: 

 

pipe diameter: 150 mm, 

 

use  the  drop  separator  so  that  the  condensate  can  leave  the  stack  duct  without  damaging 

the pipe exchanger. 

 

check the leaktightness of the stack component connections, 

 

minimal stack height: 5 metres, 

 

the stack section outside the building should be insulated (a double wall), 

 

wind should freely fan the stack outlet from all directions (the end of the stack pipe 

should be above the rooftop level), 

 

if possible, all stack sections should be vertical - horizontal sections should be avoided as well as 

stack  pipe  bends.  If  they  are  necessary  (e.g.  two  bends  if  the  pipe  runs 

through a wall or a window), the maximal bend angle equals 45° and the minimal stack height should 

be increased to 6 meters, 

 

the already existing ventilation ducts must not be used to build the stack system! 

 

CAUTION!!! 

IF  AN  ADDITIONAL  HEAT  EXCHANGER  IS  INSTALLED  ON  THE  STACK  SYSTEM  (e.g.  EXHAUST 
FUMES ECONOMISER), IT IS ADVISABLE TO CLEAN THE EXCHANGER AT LEAST ONCE A MONTH 
(depending on the fuel quality) AS ITS INNER WALLS ARE BEING COVERED WITH DUST, WHICH 
RESULTS IN A REDUCED CALORIFIC EFFECT OF THE EXCHANGER. A DECREASED DIAMETER OF 
EXHAUST FUMES FLOW WILL CAUSE AN EARLY SWITCH OF THE STOVE INTO THE “OVERFLOW” 
PHASE AS A RESULT  OF BAD COMBUSTION. Places where the stack runs through the ceiling, 
walls or the roof must be insulated so as to avoid fire hazard. It is advisable to use a two-layer 
insulated stack pipe wherever there is a possibility of touch contact and outside the building, to 
ensure constant proper draught and prevent condensation. Do not place any materials near the 
stove, even those which are non-inflammable. Ensure constant air supply, necessary for proper 
combustion process. 

Fig. 4. Stack system 

[min. 0.5 m] 

[T-connection 

150 

with drop separator] 
[acid-proof stack 

pipe 

150] 

[draught regulator 

130/

 

150] 

Содержание 52

Страница 1: ...UNIVERSAL OIL HEATER TYPE MTM 52 kW ORIGINAL MANUAL v 08 2015 ...

Страница 2: ...n Risk assessment and risk reduction EN ISO 13732 1 2008 Ergonomics of the thermal environment Methods for the assessment of human responses to contact with surfaces Part 1 Hot surfaces EN ISO 13857 2008 Safety of machinery Safety distances to prevent hazard zones being reached by upper and lower limbs EN ISO 14159 2008 Safety of machinery Hygiene requirements for the design of machinery EN 60335 ...

Страница 3: ...ical contamination 3 Use environmental conditions The universal oil heater type MTM 52 must be used in the following conditions temperature relative humidity pressure IP protection level against environmental impact good ventilation of the heated room device noise 4 Safety aspects It is inadmissible to use fuels other than specified in point 1 of the Original Manual In particular it is forbidden t...

Страница 4: ...peration until the furnace has cooled down to the temperature below 35 C The other bimetallic sensor is located on the heat exchanger as well and its threshold temperature equals 90 C Its contact opening resulting from exceeding the threshold temperature causes the stove to immediately enter the Overheating phase see point 8 in this Manual The heater is also equipped with a weight sensor located u...

Страница 5: ...amber during heater operation to provide optimal draught install an at least 5 metre long smooth vertical stack pipe resistant to high temperature not aluminium check the leaktightness of all stack connections tighten them with insulating tape if necessary make sure that the combustion bowl is located in the combustion chamber centrally place the deflector inside the combustion chamber according t...

Страница 6: ...f the pipe runs through a wall or a window the maximal bend angle equals 45 and the minimal stack height should be increased to 6 meters the already existing ventilation ducts must not be used to build the stack system CAUTION IF AN ADDITIONAL HEAT EXCHANGER IS INSTALLED ON THE STACK SYSTEM e g EXHAUST FUMES ECONOMISER IT IS ADVISABLE TO CLEAN THE EXCHANGER AT LEAST ONCE A MONTH depending on the f...

Страница 7: ...he standby phase Stop no heat is generated the fan and the pump do not operate The diode STANDBY lights on the controller in this time Pressing the button Start causes the diode OPERATION to light up and the stove to go into the firing up phase During this phase the diode OPERATION is blinking When the furnace has heated up to ca 40 C contact shorting of the control thermostat located next to the ...

Страница 8: ...peration wait until the stove has cooled down i e the fan has switched off and press the button on the casing of the bimetallic sensor Then press the Stop button which will cause the heating diode and the sound signal to turn off The stove may now be switched on again The overflow signal is generated by the micro switch located under the overflow tank The contact opening signals that the tank has ...

Страница 9: ...ether the feeding pipe burner of the device is maximally pushed to the device housing if not push it Insert the power plug in the power socket 230V 50Hz the diode STANDBY lights up Draw the top part of the heater housing aside and remove the combustion chamber cover Then take the deflector out if necessary thoroughly clean the combustion bowl the base which it is placed on and the entire combustio...

Страница 10: ...ration of the device clean the furnace bowl and other combustion chamber elements everyday before firing up The maximal device operation time without cleaning the bowl is about 7 12 hours depending on the employed oil intended for combustion check the passability of the overflow pipe the pipe in the lower part of the combustion chamber directly over the overflow bowl clean if necessary clean the c...

Страница 11: ... too thick or too cold Dilute with diesel oil Check the pump control thermostat and replace it if needed Check the motor and see if the pump is not soiled on the inside Check STB and overflow protection 5 The fuel ducts is obstructed oil returns to the tank through the primary duct Clean the fuel duct and replace it if needed 6 The pump operation control thermostat has not reached proper temperatu...