background image

6

QSG 800LR-1.8

May 2010

Linking your transmitter and receiver units

You must reset the transmitter unit to factory defaults (to disable encryption) 
before linking the transmitter and receiver units. For more information, see 
the WIO-800LT Transmitter Quick Start Guide.
NOTE: You must complete the linking process in 60 seconds.
To link the transmitter and receiver units:
1.  Press and hold down the RSSI Pushbutton on the receiver.
2.  Power on the receiver while holding down the RSSI Pushbutton
3.  Release the RSSI Pushbutton as soon as the Receiver LEDS flash (within 

5 seconds of powering the receiver).

4.  The receiver will flash all LEDs for a maximum 60 seconds while it tries to 

link to the transmitter.

5.  Power on the transmitter. The transmitter sends a special “Link” message 

to allow the receiver to recognise the transmitter.

6.  When  the  units  link,  the  receiver  lights  all  LEDs  for  2  seconds  before 

returning to normal operation.

NOTE:

  If  the  receiver  LEDs  continue  flashing  within  the  60  seconds,  the 

units are not linked and you should retry the linking process by powering the 
transmitter off and on again. If you exceed the 60 seconds, you must restart 
the linking process from step 1.
You can now bench test your configuration before deploying.

Safety information

Thank you for selecting the WIO-800LR receiver for your telemetry needs. 
We  trust  it  will  give  you  many  years  of  valuable  service.  To  ensure  your  
WIO-800LR receiver enjoys a long life, double-check ALL your connections 
with the user’s manual before powering on the unit.
WARNING: Incorrect termination of supply wires may cause internal damage 
and will void warranty.

Содержание WIO-800LR

Страница 1: ...Quick Start Guide QSG 800LR WIO 800LR wireless I O receiver unit ...

Страница 2: ...he basic steps for using your unit are 1 Connect the antenna power supply and transducer signals using the instructions in this document Power supply and transducer connection is described in the section Unit components and connections Antenna connection is described in the section Antenna installation For more information see the WIO 800L Installation Manual 2 Resetthetransmitterandreceiverunitst...

Страница 3: ...egulations this module must be installed in an Electrical AND Fire enclosure This enclosure may be a single or multiple enclosures Access to the module is to be made by a Service Person only In order to comply with Electrical Safety Standards when connecting SELV AND voltages which are greater than SELV 30VAC or 60VDC together then Relay Output 2 must NOT be used in order to provide sufficient iso...

Страница 4: ...ssed When you press the RSSI push button the unit shows the signal strength by lighting the LEDs from the bottom to the top Signal strength is the strength of the last message received that was addressed to this station LED Signal Strength LED Signal Strength D1 Better than 85 dBm RX Better than 100 dBm D2 Better than 90 dBm CF Better than 105 dBm D3 Better than 95 dBm PG Always on during RSSI tes...

Страница 5: ...0LR receiver flashes all LEDs at medium flash i e 1 6 Hz NOTE If the LEDs do not flash you must repeat steps 1 and 2 until the LEDs flash before continuing 4 Release the RSSI push button within 5 seconds 5 Within a further 60 seconds press and hold the RSSI push button for 5 seconds until the LEDs stop flashing and then release 6 The WIO 800LR receiver lights all LEDs for 2 seconds before returnin...

Страница 6: ...the transmitter The transmitter sends a special Link message to allow the receiver to recognise the transmitter 6 When the units link the receiver lights all LEDs for 2 seconds before returning to normal operation NOTE If the receiver LEDs continue flashing within the 60 seconds the units are not linked and you should retry the linking process by powering the transmitter off and on again If you ex...

Страница 7: ...n 0 1 accuracy single ended source output Power supply 1 9 30 VDC 0 25 Amp CSA certified Class 2 power supply For use in Class 1 Div 2 hazardous areas the power supply must be approved for Class 1 Div 2 use WARNING Explosion hazard do not connect or disconnect while circuit is live unless area is known to be non hazardous Radio receiver 1 High sensitivity DFSK Fixed Frequency receiver Frequency 86...

Страница 8: ...ello Balsamo MI Italy Tel 39 0 2 61802011 Fax 39 0 2 61294560 E mail info mtl inst it Cooper Crouse Hinds Japan KK MT Building 3F 2 7 5 Shiba Daimon Minato ku Tokyo Japan 105 0012 Tel 81 0 3 6430 3128 Fax 81 0 3 6430 3129 E mail sales mtlkk co jp Cooper Crouse Hinds Korea 12F Vision Tower 707 2 Yeoksam dong Gangnam gu Seoul 135 080 South Korea Tel 82 2 3484 6795 Fax 82 2 3484 6778 MTL Instruments ...

Отзывы: