Configuring the Gateway
EZ Gateway Start-up Guide
20
6.2
BMS Settings
Select appropriate protocol and enter the fields for the protocol settings described below as needed.
6.2.1 BACnet/IP and BACnet MS/TP
Parameter
Definition
All Connections
BACnet Network
The BACnet network number for the connection. Legal values are 1-65534. Each
network number must be unique across the entire BACnet internetwork.
BACnet/IP Settings
IP Port
The BACnet/IP default is 47808 (0xBAC0), but other port numbers can be specified.
BACnet MS/TP Settings
MAC Address
Legal values are 0-127, must be unique on the physical network.
Max Master
The highest MAC address to scan for other MS/TP master devices. The default of 127 is
guaranteed to discover all other MS/TP master devices on the network.
Max Info Frames
The number of transactions the BACnet Explorer may initiate while it has the MS/TP
token. Default is 50.
Baud Rate
The serial baud rate used on the network.
Figure 18: BACnet Connection Parameters
Figure 17: BACnet BMS Settings