(82A044)  TDMv1017

FIGURE 5—Operation Display & Additional Programming Options

When the unit is operating, the display will indicate which output is active for the duration of its 

programmed time delay.  For relay output #1, a 

1

 will be displayed and 

2

 will be displayed for relay output 

#2.  If the delays d3 or d4 are used (such as an installation using a Mag Lock or a Vestibule application), 

the delay will be evident between the displaying of both outputs.

In addition to the settings already described in the previous sections, below is a listing of various options 

which are programmable on the TDM.  The LED display vs. function are as follows:

––

 = Ready Mode (flashing)

d1

 = Time Delay or "ON TIME" of relay output #1—0.0 to 99 seconds

d2

 = Time Delay or "ON TIME" of relay output #2—0.0 to 99 seconds

d3

 = Time Delay between d1 and d2—0.0 to 99 seconds

d4

 = Time Delay between d2 and d1—0.0 to 99 seconds

i1

 = Switch Input #1—(N.O. or N.C.)

i2

 = Switch Input #2—(N.O. or N.C.)

i3

 = Switch Input #3—(N.O. or N.C.)

i4

 = Switch Input #4—(N.O. or N.C.)

o1

 = Relay Output #1—(N.O. or N.C.)

o2

 = Relay Output #2—(N.O. or N.C.)

- -

 = Error (flashing)

The 

PUSHBUTTON FAULT INDICATOR

 is a special feature designed to alert the installer if a pushbutton is 

"stuck" in the active position or if the wires have shorted.  If this occurs, the display will flash double dots 

(

 

.

 

.

 

).  Additionally, this could mean that the wiring did not match the programmed parameter.  In other 

words, the unit may be programmed for use with a normally open switch, but may be wired to a normally 

closed switch.  Normal operation will resume once the fault condition has been cleared.

WET/DRY CONTACT OPTION:

The TDM has the option of supplying power to relay output #1 contacts.  This is known as "WET" contacts 

instead of the conventional "DRY" contacts or simple contact closure.  Providing this voltage can simplify 

the wiring of installations where an Electric Locking  device is used.  However, the voltage supplied to the 

output is the same voltage supplied to the input of the TDM and must be compatible with the Locking 

device to be controlled.  Please contact the factory for additional information.

                             Universal Time Delay Module 

INSTALLATION INSTRUCTIONS

The 

Commander

Series

TDM

7898 Zionsville Road 

 Indianapolis, Indiana 46268

Telephone: (317) 842-2545 

 www.mssedco.com 

 [email protected]

Содержание TDM

Страница 1: ...ns are included Figure 2 Simple Time Delayed Output Figure 3 Electric Lock Door Operator Sequencing Figure 4 Vestibule Door Sequencing Detailed Operating Display functions for the TDM are shown in Figure 5 For additional technical assistance contact us toll free at 1 317 842 2545 Figure 5 TDM Operating Display Function NOTICE These instructions are provided for your convenience Please verify your ...

Страница 2: ...044 TDMv1017 FIGURE 1 TDM Layout Wiring Connections Input Connections Wht Brown Wht Vio Wht Grn Wht Red Wht Blue Blue Green Green Wht Gray Input Power 12 24V AC or DC Switch Input 1 Switch Input 2 Switch Input 3 Switch Input 4 Output Connections Orange Brown Yellow Violet White Gray Output 2 Output 1 COM N O N C COM N O N C Input Actions Input 1 Sequences Output 1 then Output 2 Input 2 Sequences O...

Страница 3: ...hanged make the change to the d1 setting press the PROGRAM MODE BUTTON once and then wait 30 seconds until the double bars appear again 5 During operation of the unit the display will indicate its operating status Please refer to Figure 5 at the end of this installation manual or Electric Exit Device Wall Switch PUSH TO OPEN WHT RED WHT VIO MS SEDCO TDM Timing Control Module N C Output 1 Input 3 S...

Страница 4: ...e door This time is usually set around 0 5 1 second Again adjust the setting and then depress the PROGRAM MODE BUTTON The display should now read d4 Now wait 30 seconds until the double bars appear indicating that the unit is in its normal operating ready mode NOTE d1 should be longer than d3 3 You are now ready to test your installation If any of the time settings need to be changed make the chan...

Страница 5: ... is the delay time between the opening of the doors going in the opposite direction Adjust this value in the same manner as before When the PROGRAM MODE BUTTON is depressed i1 will then be displayed Now wait 30 seconds until the double bars appear indicating that the unit is in its normal operating ready mode 3 You are now ready to test your installation If any of the time settings need to be chan...

Страница 6: ...o2 Relay Output 2 N O or N C Error flashing The PUSHBUTTON FAULT INDICATOR is a special feature designed to alert the installer if a pushbutton is stuck in the active position or if the wires have shorted If this occurs the display will flash double dots Additionally this could mean that the wiring did not match the programmed parameter In other words the unit may be programmed for use with a norm...

Отзывы: