FIGURE 2—Simple Time Delayed Output

Once the TDM has been wired for the above application, programming of the device is as follows:

1)  Apply power to the unit, provided there is no smoke or fire, you can assume that your wiring job must 

 

be somewhat successful.

2)  Once properly powered, the display will flash double bars (

––

) indicating that the unit is in its normal 

 

operating ready mode.

3)  To begin programming, depress the 

PROGRAM MODE BUTTON

 one time.  The first parameter to be 

 

programmed will appear on the display.  This is the delay time, or "on time" of the output #1 and is 

 

displayed as 

d1

 followed by the time setting (It will flash between the two).  To adjust the time setting, 

 

use a small screwdriver and rotate the 

DISPLAY ADJUSTMENT

 clockwise to increase and 

 

counterclockwise to decrease the time setting.  After the desired value is displayed, depress the 

 

PROGRAM MODE BUTTON

 again to save the value.  The display will now read 

d2

.  Now wait 30 

 

seconds until the display again reads double bars (

––

) indicating that the unit is in its normal 

 

operating ready mode.

4)  You are now ready to test your installation.  If the time delay has to be changed, make the change to 

 the 

d1

 setting, press the 

PROGRAM MODE BUTTON

 once and then wait 30 seconds until the double 

 

bars (

––

) appear again.

5)  During operation of the unit, the display will indicate its operating status.  Please refer to Figure 5 at 

 

the end of this installation manual.

or Electric Exit Device

Wall

Switch

PUSH

TO 

OPEN

WHT/RED

WHT/VIO

MS SEDCO

TDM

Timing Control Module

N.C.

Output #1

Input #3

SPRINKLER

OR FIRE

DETECTION

SYSTEM

(IF USED)

FIRE

SYSTEM

(IF USED)

PROTECTION

SIGNALING

Mag Lock

N.C.

N.C.

AC / DC

GRN

GRN

GRAY

VIO

JUMPER

INSTALLED 

FOR "DRY"

CONTACTS

12-24V

12-24V

This separate power source ( & associated wiring) can be eliminated 

if the jumper is set for "WET" contacts instead of "DRY" contacts.

(see page 6)

TDM

INPUT 

4

INPUT 

3

INPUT 

2

INPUT 

1

12-24V AC/DC

INPUT 

1

COM

COM

COM

COM

N.

O.

N.

C.

N.

C.

N.

O.

PROGRAM

MODE BUTTON

DISPLAY

ADJUSTMENT

LED DISPLAY KEY

d1 = delay 1

d2 = delay 2

d3 = delay d1 to d2

d4 = delay d2 to d1

i1 = input 1 (n.o. / n.c.)

i3 = input 3 (n.o. / n.c.)

i2 = input 2 (n.o. / n.c.)

i4 = input 4 (n.o. / n.c.)

o2 = output 2 (n.o. / n.c.)

o1 = output 1 (n.o. / n.c.)

o1= dr

y

o1= wet

Output #1

Output #2

PROGRAMMING 

PROCEDURE

NOTE:

  Mag Lock uses N.C. 

  (Gray & Violet)

 

  Electric Exit device uses 

  N.O. (Gray & White)

                             Universal Time Delay Module 

INSTALLATION INSTRUCTIONS

The 

Series

TDM

Commander

7898 Zionsville Road 

 Indianapolis, Indiana 46268

Telephone: (317) 842-2545 

 www.mssedco.com 

 [email protected]

Содержание TDM

Страница 1: ...ns are included Figure 2 Simple Time Delayed Output Figure 3 Electric Lock Door Operator Sequencing Figure 4 Vestibule Door Sequencing Detailed Operating Display functions for the TDM are shown in Figure 5 For additional technical assistance contact us toll free at 1 317 842 2545 Figure 5 TDM Operating Display Function NOTICE These instructions are provided for your convenience Please verify your ...

Страница 2: ...044 TDMv1017 FIGURE 1 TDM Layout Wiring Connections Input Connections Wht Brown Wht Vio Wht Grn Wht Red Wht Blue Blue Green Green Wht Gray Input Power 12 24V AC or DC Switch Input 1 Switch Input 2 Switch Input 3 Switch Input 4 Output Connections Orange Brown Yellow Violet White Gray Output 2 Output 1 COM N O N C COM N O N C Input Actions Input 1 Sequences Output 1 then Output 2 Input 2 Sequences O...

Страница 3: ...hanged make the change to the d1 setting press the PROGRAM MODE BUTTON once and then wait 30 seconds until the double bars appear again 5 During operation of the unit the display will indicate its operating status Please refer to Figure 5 at the end of this installation manual or Electric Exit Device Wall Switch PUSH TO OPEN WHT RED WHT VIO MS SEDCO TDM Timing Control Module N C Output 1 Input 3 S...

Страница 4: ...e door This time is usually set around 0 5 1 second Again adjust the setting and then depress the PROGRAM MODE BUTTON The display should now read d4 Now wait 30 seconds until the double bars appear indicating that the unit is in its normal operating ready mode NOTE d1 should be longer than d3 3 You are now ready to test your installation If any of the time settings need to be changed make the chan...

Страница 5: ... is the delay time between the opening of the doors going in the opposite direction Adjust this value in the same manner as before When the PROGRAM MODE BUTTON is depressed i1 will then be displayed Now wait 30 seconds until the double bars appear indicating that the unit is in its normal operating ready mode 3 You are now ready to test your installation If any of the time settings need to be chan...

Страница 6: ...o2 Relay Output 2 N O or N C Error flashing The PUSHBUTTON FAULT INDICATOR is a special feature designed to alert the installer if a pushbutton is stuck in the active position or if the wires have shorted If this occurs the display will flash double dots Additionally this could mean that the wiring did not match the programmed parameter In other words the unit may be programmed for use with a norm...