background image

5

mselectronics.co.uk

Installation

All electrical installation and maintenance must be carried out by a competent person. If in doubt, 

consult a qualified electrician. Any new wiring must be carried out by qualified personnel in 

accordance with the current edition of the IET Wiring Regulations (BS7671).

!

 

Ensure the electrical supply is isolated before making any connections or adjustments.

!

1.  Prepare a single-gang pattress or back box as necessary.

2.  Rotate the 

Timeout

 thumbwheel (referring to the accompanying label) to set the period 

of time for which the load should remain switched on after a contact closure trigger.

3.  Connect the wiring as shown in Figure 2 (or in any suitably appropriate form).

− 

Supply connections (L, N):

 Use appropriate mains cable to power the unit. If the 

load is also powered via this wiring, ensure the current rating is adequate. Otherwise 

(i.e. if the output is independently powered), low-current cable may be used.

− 

Load connections (LIVE IN, LIVE OUT):

 Use cable rated for the load current and 

voltage.

− 

Remote input connections (V+, R+, R-):

 Low-current cable may be used but 

must 

be rated for mains voltages

. Refer to 

Remote Input Wiring

 for wiring details for 

different input devices.

4.  Fix the unit into position with the two screws and caps supplied. 

Additional Guidelines

• 

The screw caps may be removed at a later date with the aid of an adhesive putty such 

as Blu-Tack.

Содержание RTDS3

Страница 1: ...Product Guide RTDS3 today tomorrow and in the future mselectronics co uk Remote Time Delay Switch 3 wire version energy saving controls Issue 1 0...

Страница 2: ...g energy by switching it off automatically when not required after an adjustable period At any time the activation period may be extended with a further brief contact closure or cancelled by an extend...

Страница 3: ...for inline connection with the load to be switched no neutral required such as to replace a standard light switch A minimum load of 20W per switch unit applies a load capacitor is required for smaller...

Страница 4: ...observed with relevance to the particular installation Referring to the steps under Installation connect the remote input s as follows TDS S Use 3 core mains rated cable and connect as shown below Fi...

Страница 5: ...ter a contact closure trigger 3 Connect the wiring as shown in Figure 2 or in any suitably appropriate form Supply connections L N Use appropriate mains cable to power the unit If the load is also pow...

Страница 6: ...RTDS3 6 Operation The diagram below illustrates the sequence of operation for the unit Key Sequence of Operation...

Страница 7: ...on a Unit is not powered Ensure the unit is correctly connected to an active mains supply b Load is not connected correctly Ensure the load is connected appropriately The relay output is volt free so...

Страница 8: ...onics co uk or call 0333 666 1176 Alternatively email techsupport mselectronics co uk Additional copies of this product guide can be downloaded from our website Product Warranty MS Electronics guarant...

Отзывы: