background image

RTDS3

4

Remote Input Wiring

Up to five inputs may be connected in parallel to control the unit. Each input device may be 

either a volt-free relay output, a normally-open mechanical switch (such as a pushbutton or 

retractive rocker), or a TDS-S slave unit, which provides a touch-sensitive button.

Do not apply any voltages to the remote input terminals.

!

The following wiring example is intended only as a recommendation. Proper wiring practice must be 

observed with relevance to the particular installation.

!

Referring to the steps under 

Installation

, connect the remote input(s) as follows.

• 

TDS-S:

 Use 3-core mains-rated cable and connect as shown below. Figure 3 illustrates 

a typical wiring example using two TDS-S slave units; Figure 4 represents the same 

configuration as applied to a typical ceiling rose lighting circuit.

• 

Relays and other switches:

 Use 2-core mains-rated cable and connect to the 

R+

 and 

R-

 terminals only (polarity does not matter); do not use the 

V+

 terminal.

Figure 3

 

Typical wiring schematic using two TDS-S slave units

Figure 4

 

Typical ceiling rose plan using two TDS-S slave units

Содержание RTDS3

Страница 1: ...Product Guide RTDS3 today tomorrow and in the future mselectronics co uk Remote Time Delay Switch 3 wire version energy saving controls Issue 1 0...

Страница 2: ...g energy by switching it off automatically when not required after an adjustable period At any time the activation period may be extended with a further brief contact closure or cancelled by an extend...

Страница 3: ...for inline connection with the load to be switched no neutral required such as to replace a standard light switch A minimum load of 20W per switch unit applies a load capacitor is required for smaller...

Страница 4: ...observed with relevance to the particular installation Referring to the steps under Installation connect the remote input s as follows TDS S Use 3 core mains rated cable and connect as shown below Fi...

Страница 5: ...ter a contact closure trigger 3 Connect the wiring as shown in Figure 2 or in any suitably appropriate form Supply connections L N Use appropriate mains cable to power the unit If the load is also pow...

Страница 6: ...RTDS3 6 Operation The diagram below illustrates the sequence of operation for the unit Key Sequence of Operation...

Страница 7: ...on a Unit is not powered Ensure the unit is correctly connected to an active mains supply b Load is not connected correctly Ensure the load is connected appropriately The relay output is volt free so...

Страница 8: ...onics co uk or call 0333 666 1176 Alternatively email techsupport mselectronics co uk Additional copies of this product guide can be downloaded from our website Product Warranty MS Electronics guarant...

Отзывы: