Installation Instructions and Owner’s Manual

Universal Unvented Room Heater

FLOOR MOUNTING AWAY FROM WALL:
Installing Support Feet (See figure 11.)

1.  Lay heater onto table on its back with bottom 

edge overhanging table edge.

2.  Securely attach feet to bottom of heater using 2 – 

self-tapping screws each.

Figure 11

Note: Feet should have long end going out the front of 
heater, and the edge coinciding with side of heater. If 
feet overhang side of the heater, switch leg location.

3.  Place heater on non-combustible surface (see 

Locating Heater, page 6) before proceeding 
with gas connection. If this will be a permanent 
location, heater may be locked into position using 
anchoring holes in mounting feet.

Note: Use of floor mounting feet will require you to 

use a 3/8 NPT street elbow to make gas connection.

DUAL FUEL CAPABILITY

This appliance can be used with propane or natural gas. 
The factory has set the heater up for propane operation 
by default. If using propane, remove the plug from the 
Propane/LP regulator and do not make any further 
adjustments. If converting for use with Natural Gas See 

“FUEL CONVERSION INSTRUCTIONS” on page 11 before 

proceeding. 

NATURAL GAS

CAUTION: Never connect heater to private (non-utility) 

gas well. This gas is commonly known as well-head 

gas. 

IMPORTANT: Check your gas line pressure before 
connecting heater to gas line. Gas line pressure must be 
no greater than 10.5 inches of water. If gas line pressure 
is higher, heater regulator damage could occur.

PROPANE/LP

CAUTION: Never connect heater directly to the 

Propane supply. This heater requires an external 
regulator (not supplied). Install the external regulator 
between the heater and Propane/LP supply. 

The installer must supply an external regulator. The 
external regulator will reduce the incoming gas pressure 
to between 11 and 14 inches of water. If you do not 
reduce incoming gas pressure heater regulator damage 
could occur. Install external regulator with the vent 
pointing down. Pointing the vent down protects it from 
freezing rain or sleet.

CONNECTING TO GAS SUPPLY

WARNING: A qualified service person must connect heater 

to gas supply. Follow all local codes. 

WARNING: This appliance requires a 3/8” NPT (National 

Pipe Thread) inlet connection to the pressure regulator. 

Use of floor mounting feet will require you to use a 3/8 

NPT street elbow to make gas connection. 

CAUTION: Two gas line installations at the same time are 

prohibited. The access plate to the switching means shall 
not be opened while the heater is in operation.

CAUTION: Use only new black iron or steel pipe. Internally-

tinned copper tubing may be used in certain areas. Check your 
local codes. Use pipe of large enough diameter to allow proper 
gas volume to heater. If pipe is too small, undue loss of pressure 
will occur. 
Installation must include an equipment shutoff valve, union 

and plugged 1/8” NPT tap. Locate NPT tap within reach of test 

gauge hookup. NPT tap must be upstream from heater (see 

figure 12).
*A CSA/AGA certified equipment shutoff valve with 1/8” 

NPT tap is an acceptable alternative to test gauge connection. 
Purchase the CSA/AGA certified equipment shutoff valve from 
your dealer. 
IMPORTANT: Install an equipment shutoff valve in an accessible 
location. The equipment shutoff valve is for turning on or 
shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male threads. This will prevent 
excess sealant from going into pipe. Excess sealant in pipe could 
result in clogged heater fuel train. Sealant will also help reduce 
the chance of cross threading.

CAUTION: Use pipe joint sealant that is resistant to Propane/LP 
 and/or Natural Gas depending on fuel used.

Install sediment trap in supply line as shown in figure 12. Locate 

sediment trap where it is within reach for cleaning. A sediment 
trap traps moisture and contaminants. This keeps them from 
going into heater. If sediment trap is not installed or is installed 
improperly, heater may not run correctly.
IMPORTANT: Hold pressure regulator with wrench when 
connecting it to gas piping and/or fittings.

Nipple

Tee Joint

Cap

Shutoff Valve

HEATER CABINET

Nipple

Nipple

Tee Joint

Ground Joint Union

3/8” NPT Pipe Nipple

Pressure 
Regulator

Test Gauge
Connection

1/8” NPT Plug Tap

Reducer Bushing
to 1/8” NPT

Nipple

Sediment 
Trap

3” minimum

Regulated NG Line

(7.5”W.C to 14”WC Pressure)

OR

Regulated LP (Propane) Tank

(11”W.C to 14”WC Pressure)

Figure 12

Содержание MHVFDF10BF

Страница 1: ...the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier T...

Страница 2: ...including benzene which is known to the state of California to cause cancer and cause birth defects or other reproductive harm for more information go to www P65Warnings ca gov Due to high temperature...

Страница 3: ...servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liquids or vapors are used or stored During dusty conditions 7 Before using furniture po...

Страница 4: ...s Code or applicable local codes 3 Add the Btu hr of all the fuel burning appliances in the space such as Vent free heater Gas water heater Gas furnace Vented gas heater Gas fireplace logs and Other g...

Страница 5: ...ion and Ventilation for required size of ventilation grills or ducts WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh air to supply...

Страница 6: ...floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth...

Страница 7: ...using 5 16 drill bit For solid walls concrete or masonry drill at least 1 deep 2 Fold wall anchor as shown in figure 8 below 3 Insert wall anchor wings first into hole Tap anchor flush to wall 4 For t...

Страница 8: ...ust connect heater to gas supply Follow all local codes WARNING This appliance requires a 3 8 NPT National Pipe Thread inlet connection to the pressure regulator Use of floor mounting feet will requir...

Страница 9: ...opane LP supply valve 3 Check all joints from the propane LP supply valve to equipment shutoff valve see figure 14 Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 4 Co...

Страница 10: ...supplier for repairs Until repairs are made light pilot with match 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If pilot does not stay lit r...

Страница 11: ...he can you could damage the burner or pilot assembly In addition the directions below should also be followed 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes...

Страница 12: ...ose at control valve Hand tighten thermocouple nut until snug and then tighten 1 4 turn more Pilot flame not touching thermocouple which allows thermocouple to cool causing pilot flame to go out This...

Страница 13: ...clearances see Figure 4 page 6 Dirty or partially clogged burner orifice Clean burner orifice see Cleaning and Maintenance on page 1 1 or replace burner orifice White powder residue forming within bu...

Страница 14: ...e purchased at any Mr Heater Products local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 866 447 2194 WWW HEATSTARBYENERCO COM Our office hours are 8 00 AM...

Отзывы: