MrHeater MHVFDF10BF Скачать руководство пользователя страница 5

5

Installation Instructions and Owner’s Manual

Universal Unvented Room Heater

*Do not include direct-vent gas appliances. Direct-vent 

draws combustion air from the outdoors and vents to 
the outdoors.
Example:
Gas water heater 

40,000 Btu/hr

Vent Free   20,000 Btu/hr

Total 

 

=60,000 Btu/hr

4.  Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example: 51,800 Btu/hr (maximum Btu/hr the    

 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined space 
because the actual Btu/hr used is more than the 
maximum Btu/hr the space can support.

You must provide additional fresh air. Your options are as 
follows:
A. Rework worksheet, and the space of an adjoining room. 

If the extra space provides an unconfined space, remove 
door to adjoining room or add ventilation grills between 

the rooms. See Ventilation From Inside Building (Fig. 2)

B.  Vent room directly to the outdoors. See Ventilation 

From Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size makes 

room unconfined. 

If actual Btu/hr used is less than the maximum Btu/
hr the space can support, the space is an unconfined 
space. You will need no additional fresh air ventilation.

VENTILATION AIR

Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 
space. When ventilation to an adjoining unconfined space, 
you must provide two permanent openings: one within 

12” of the ceiling and one within 12” of the floor on the 
wall connecting the two spaces (see options 1 & 2 of figure 
2). You can also remove door into adjoining room (see 
option3, fig 2). Follow the National Fuel Gas Code NFPA 
54/ ANSI Z223.1, Section 5.3, Air for Combustion and 

Ventilation for required size of ventilation grills or ducts.

WARNING: Rework worksheet, adding the space of 

the adjoining unconfined space. The combined space 
must have enough fresh air to supply all appliance in 
both spaces. 

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation grills 
or ducts. Connect these items directly to the outdoors or 
spaces open to the outdoors. These include attics* and 
crawl spaces. Follow the National Fuel Gas Code NFPA 

54/ ANSI Z223.1, Section 5.3, Air for Combustion and 

Ventilation for required size of ventilation grills or ducts.

Ventilation 
Gills into 
Adjoining 

Room - 

Option 1

Ventilation Gills into Adjoining 

Room - Option 2

12”

12”

Or remove 
door into 
Adjoining 

Room - 

Option 3

Figure 2

INLET 
AIR

OUTLET 
AIR

VENTILATION CRAWL SPACE

TO CRAWL 
SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 
ATTIC

OUTLET AIR

Figure 3.

*IMPORTANT: Do not provide openings for inlet or 

outlet into attic. If attic has a thermostat-controlled power 

vent, heated air entering the attic will activate the power 
vent.

IMPORTANT: Vent-free heaters add moisture to the 

air. Although this is beneficial, installing heater in rooms 
without enough ventilation air may cause mildew to form 
from too much moisture. See 

Fresh Air for Combustion 

and Ventilation

, page 4. 

INSTALLATION

WARNING: Any change to this heater or its controls 

can be dangerous.

NOTICE: 

This heater is intended for the use as 

supplemental heat.

 Use this heater along with your 

primary heating system. Do not install this heater as your 
primary heat source. If you have a central heating system, 

you may run system’s circulating blower while using heater. 

This will help circulate the heat throughout the house. In 
the event of a power outage, you can use this heater as 
your primary heat source for the duration of the outage. 

WARNING: A qualified service person must install 

heater. Follow all local codes. 

Содержание MHVFDF10BF

Страница 1: ...the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier T...

Страница 2: ...including benzene which is known to the state of California to cause cancer and cause birth defects or other reproductive harm for more information go to www P65Warnings ca gov Due to high temperature...

Страница 3: ...servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liquids or vapors are used or stored During dusty conditions 7 Before using furniture po...

Страница 4: ...s Code or applicable local codes 3 Add the Btu hr of all the fuel burning appliances in the space such as Vent free heater Gas water heater Gas furnace Vented gas heater Gas fireplace logs and Other g...

Страница 5: ...ion and Ventilation for required size of ventilation grills or ducts WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh air to supply...

Страница 6: ...floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth...

Страница 7: ...using 5 16 drill bit For solid walls concrete or masonry drill at least 1 deep 2 Fold wall anchor as shown in figure 8 below 3 Insert wall anchor wings first into hole Tap anchor flush to wall 4 For t...

Страница 8: ...ust connect heater to gas supply Follow all local codes WARNING This appliance requires a 3 8 NPT National Pipe Thread inlet connection to the pressure regulator Use of floor mounting feet will requir...

Страница 9: ...opane LP supply valve 3 Check all joints from the propane LP supply valve to equipment shutoff valve see figure 14 Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 4 Co...

Страница 10: ...supplier for repairs Until repairs are made light pilot with match 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If pilot does not stay lit r...

Страница 11: ...he can you could damage the burner or pilot assembly In addition the directions below should also be followed 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes...

Страница 12: ...ose at control valve Hand tighten thermocouple nut until snug and then tighten 1 4 turn more Pilot flame not touching thermocouple which allows thermocouple to cool causing pilot flame to go out This...

Страница 13: ...clearances see Figure 4 page 6 Dirty or partially clogged burner orifice Clean burner orifice see Cleaning and Maintenance on page 1 1 or replace burner orifice White powder residue forming within bu...

Страница 14: ...e purchased at any Mr Heater Products local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 866 447 2194 WWW HEATSTARBYENERCO COM Our office hours are 8 00 AM...

Отзывы: