5
Operating Instructions and Owner’s Manual
Mr. Heater | Unvented Natural Gas Fired Room Heater
NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING!
NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING!
NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING!
Figure 2
Figure 3
INST
ALLATION
WARNING:
Rework worksheet,
adding the space of the adjoining
unconfined space. The combined space
must have enough fresh air to supply all
appliance in both spaces.
*IMPORTAN
T:
Do not provide
openings for inlet or outlet into attic. If
attic has a thermostat-controlled power
vent, heated air entering the attic will
activate the power vent.
IMPORTANT:
Vent-free heaters
add moisture to the air. Although
this is beneficial, installing heater in
rooms without enough ventilation air
may cause mildew to form from too
much moisture. See
Fresh Air for
Combustion and Ventilation
, pages
4 through 5.
WARNING:
Any change to this
heater or its controls can be dangerous.
WARNING: A qualified service
person must install heater. Follow all
local codes.
*Do not include direct-vent gas
appliances. Direct-vent draws
combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater 40,000 Btu/
hr
Vent Free 20,000 Btu/
hr
Total
=60,000 Btu/hr
4. Compare the maximum Btu/hr the
space can support with the actual
amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum
Btu/hr the space can support)
6 0 , 0 0 0 B t u / h r ( A c t u a l
a m o u n t o f B t u / h r u s e d )
The space in the above example is a
confined space because the actual
Btu/hr used is more than the maximum
Btu/hr the space can support.
You must provide additional fresh
air. Your options are as follows:
a. Rework worksheet, and the space
of an adjoining room. If the extra
space provides an unconfined space,
remove door to adjoining room or add
ventilation grills between the rooms.
See Ventilation From Inside Building
(Fig. 2)
b. Vent room directly to the outdoors.
See Ventilation From Outdoors (Fig.
3).
c. Install a lower Btu/hr heater if lower
Btu/hr size makes room unconfined.
If actual Btu/hr used is less than
the maximum Btu/hr the space can
support, the space is an unconfined
space. You will need no additional
fresh air ventilation.
Ventilation Air
Ventilation from Inside Building
This fresh air would come from
an adjoining unconfined space.
When ventilation to an adjoining
unconfined space, you must provide
two permanent openings: one within
12” of the ceiling and one within 12”
of the floor on the wall connecting
the two spaces (see options 1 & 2 of
Ventilated
Attic
To Attic
To Crawl
Space
Inlet Air
Ventilation Crawl Space
Ventilation Air
Outlet Air
Ventilation Grills into Adjoining
Room-Option 2
Or remove
door into
Adjoining
Room-
Option 3
Ventilation
Grills into
Adjoining
Room-
Option 1
(30.5 cm) 12”
12” (30.5 cm)
figure 2). You can also remove door
into adjoining room (see option3, fig
2). Follow the National Fuel Gas Code
NFPA 54/ ANSI Z223.1, Section 5.3,
Air for Combustion and Ventilation
for required size of ventilation grills or
ducts.
Ventilation from Outdoors
If necessary provide extra fresh air
by using ventilation grills or ducts.
Connect these items directly to the
outdoors or spaces open to the
outdoors. These include attics* and
crawl spaces. Follow the National Fuel
Gas Code NFPA 54/ ANSI Z223.1,
Section 5.3, Air for Combustion
and Ventilation for required size of
ventilation grills or ducts.
INSTALLATION
NOTICE: This heater is intended for
the use as supplemental heat.
Use
this heater along with your primary
heating system. Do not install this
heater as your primary heat source.
If you have a central heating system,
you may run system’s circulating
blower while using heater. This will
help circulate the heat throughout the
house. In the event of a power outage,
you can use this heater as your primary
heat source for the duration of the
outage.
Check Gas Type
Use only natural gas. If your gas supply
is not natural gas, do not install heater.
Call dealer where you bought heater
for proper type heater.
This Installation Requires:
Before installing heater, make sure you
have the items listed below:
• Piping (check local codes)
• Sealant (resistant to natural gas)
• Equipment shutoff valve*
• Ground joint union
• Test gauge connection*
• Sediment trap
• Tee joint
• Pipe wrench
*A CSA/AGA certified equipment
shutoff valve with 1/8” NPT tap is an
acceptable alternative to test gauge
connection. Purchase a CSA/AGA
certified equipment shutoff valve from
your dealer.