MrHeater MHVFBF10NGT Скачать руководство пользователя страница 5

5

Operating Instructions and Owner’s Manual

Mr. Heater | Unvented Natural Gas Fired Room Heater

NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING!

NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING!

NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING!

Figure 2

Figure 3

INST

ALLATION

WARNING: 

Rework worksheet, 

adding the space of the adjoining 
unconfined space. The combined space 
must have enough fresh air to supply all 
appliance in both spaces. 

*IMPORTAN

T:

 Do not provide 

openings for inlet or outlet into attic. If 
attic has a thermostat-controlled power 
vent, heated air entering the attic will 
activate the power vent.

IMPORTANT:

 Vent-free heaters 

add moisture to the air. Although 
this is beneficial, installing heater in 
rooms without enough ventilation air 
may cause mildew to form from too 
much moisture. See 

Fresh Air for 

Combustion and Ventilation

, pages 

4 through 5. 

WARNING: 

Any change to this 

heater or its controls can be dangerous.

WARNING: A qualified service 

person must install heater. Follow all 
local codes. 

*Do not include direct-vent gas 
appliances. Direct-vent draws 
combustion air from the outdoors 
and vents to the outdoors.
Example:
Gas water heater      40,000 Btu/
hr
Vent Free    20,000 Btu/
hr
Total 

          =60,000 Btu/hr

4.  Compare the maximum Btu/hr the 

space can support with the actual 
amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum 
Btu/hr the space can support)

6 0 , 0 0 0 B t u / h r   ( A c t u a l 
a m o u n t   o f   B t u / h r   u s e d ) 
The space in the above example is a 
confined space because the actual 
Btu/hr used is more than the maximum 
Btu/hr the space can support.

You must provide additional fresh 
air. Your options are as follows:

a.  Rework worksheet, and the space 

of an adjoining room. If the extra 
space provides an unconfined space, 
remove door to adjoining room or add 
ventilation grills between the rooms. 
See Ventilation From Inside Building 
(Fig. 2)

b.  Vent room directly to the outdoors. 

See Ventilation From Outdoors (Fig. 
3). 

c.  Install a lower Btu/hr heater if lower 

Btu/hr size makes room unconfined.  
If actual Btu/hr used is less than 
the maximum Btu/hr the space can 
support, the space is an unconfined 
space. You will need no additional 
fresh air ventilation.

Ventilation Air

Ventilation from Inside Building

This fresh air would come from 
an adjoining unconfined space. 
When ventilation to an adjoining 
unconfined space, you must provide 
two permanent openings: one within 
12” of the ceiling and one within 12” 
of the floor on the wall connecting 
the two spaces (see options 1 & 2 of 

Ventilated 
Attic

To Attic

To Crawl 
Space

Inlet Air

Ventilation Crawl Space

Ventilation Air

Outlet Air

Ventilation Grills into Adjoining 
Room-Option 2

Or remove 
door into 
Adjoining 
Room-
Option 3

Ventilation 
Grills into 
Adjoining 
Room-
Option 1

(30.5 cm) 12”

12” (30.5 cm)

figure 2). You can also remove door 
into adjoining room (see option3, fig 
2). Follow the National Fuel Gas Code 
NFPA 54/ ANSI Z223.1, Section 5.3, 
Air for Combustion and Ventilation 
for required size of ventilation grills or 
ducts.

Ventilation from Outdoors

If necessary provide extra fresh air 
by using ventilation grills or ducts. 
Connect these items directly to the 
outdoors or spaces open to the 
outdoors. These include attics* and 
crawl spaces. Follow the National Fuel 
Gas Code NFPA 54/ ANSI Z223.1, 
Section 5.3, Air for Combustion 
and Ventilation for required size of 
ventilation grills or ducts.

INSTALLATION

NOTICE: This heater is intended for 
the use as supplemental heat. 

Use 

this heater along with your primary 
heating system. Do not install this 
heater as your primary heat source. 
If you have a central heating system, 
you may run system’s circulating 
blower while using heater. This will 
help circulate the heat throughout the 
house. In the event of a power outage, 
you can use this heater as your primary 
heat source for the duration of the 
outage. 

Check Gas Type

Use only natural gas. If your gas supply 
is not natural gas, do not install heater. 
Call dealer where you bought heater 
for proper type heater.

This Installation Requires:

Before installing heater, make sure you 
have the items listed below:
•  Piping (check local codes)
•  Sealant (resistant to natural gas)
•  Equipment shutoff valve*
•  Ground joint union
•  Test gauge connection*
•  Sediment trap
•  Tee joint
•  Pipe wrench
*A CSA/AGA certified equipment 
shutoff valve with 1/8” NPT tap is an 
acceptable alternative to test gauge 
connection. Purchase a CSA/AGA 
certified equipment shutoff valve from 
your dealer.

Содержание MHVFBF10NGT

Страница 1: ...e or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch...

Страница 2: ...rating the heater Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent...

Страница 3: ...been underwater Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been underwater 9 Operating heat...

Страница 4: ...lings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or less with openings gasketed or sealed and 2 Weather stripping has...

Страница 5: ...onfined space You will need no additional fresh air ventilation Ventilation Air Ventilation from Inside Building This fresh air would come from an adjoining unconfined space When ventilation to an adj...

Страница 6: ...s are 16 inches apart Attach mounting bracket to wall in one of two following ways 1 Attach to wall studs 2 Attach to wall anchor Decide which way best suits your needs Either method will provide a se...

Страница 7: ...rk screws locations on wall 3 Remove heater from mounting bracket 4 If installing bottom mounting screw into hollow or solid wall install wall anchors Follow steps 1 through 4 under Attaching to Wall...

Страница 8: ...pliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ps...

Страница 9: ...ctly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Shut...

Страница 10: ...ilot Position CAUTION Do not try to adjust heating level by using equipment shutoff valve To Turn Off Gas To Appliance SHUTTING OFF HEATER 1 Turn off equipment shutoff valve 2 Turn control knob clockw...

Страница 11: ...s vacuum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit every 2 500 hours of operation or every three months We...

Страница 12: ...l the fire department SYMPTOM SYMPTOM When ignitor button is pressed in there is a spark at the ODS pilot but no ignition When igniter button is pressed in there is no spark at pilot CAUSE CAUSE REMED...

Страница 13: ...as regulator 7 Thermocouple connection loose at control valve 7 Hand tighten thermocouple nut until snug and then tighten 1 4 turn more 8 Pilot flame not touching thermocouple which allows thermocoupl...

Страница 14: ...lly clogged 3 Clean ODS pilot see Cleaning and Maintenance page 11 1 Gas leak See WARNING statement at top of page 12 1 Locate and correct all leaks see Checking Gas Connections page 9 2 Control valve...

Страница 15: ...o Fresh Air for Combustion and Ventilation on pages 3 5 REMEDY SYMPTOM Heater produces a clicking ticking noise just after burner is lit or shut off CAUSE 1 Metal expanding while heating or contractin...

Страница 16: ...01 Orifice 1 9 80084 Regulator 1 10 80055 Regulator Mounting Bracket 1 11 80058 Floor Mounting Feet Beige 1 Item Part No Description 80214 Floor Mounting Feet White 1 12 NA Regulator Connection 1 13 8...

Страница 17: ...84 Regulator 1 7 80055 Regulator Mounting Bracket 1 8 80058 Floor Mounting Feet Beige 1 80214 Floor Mounting Feet White 1 Item Part No Description 9 NA Regulator Connection 1 10 80036 Wall Mounting Br...

Страница 18: ...Natual Gas Fired Room Heater Operating Instructions and Owner s Manual NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING NEVER LEAVE THE HEATER UNATTENDE...

Страница 19: ...ons and Owner s Manual Mr Heater Unvented Natural Gas Fired Room Heater NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING NEVER LEAVE THE HEATER UNATTENDE...

Страница 20: ...AM 5 00 PM EST Monday through Friday Please include the model number date of purchase and description of problem in all communication LIMITED WARRANTY Mr Heater Inc warrants its heaters and accessorie...

Отзывы: