8 Technical data
Maschinenfabrik Reinhausen GmbH 2020
63
4349312/01 EN
VACUTAP
®
VV
®
Sealing material
(oil – air)
VITON
Permitted pressure range
(absolute pressure)
1 bar…6 bar, vacuum not permitted
Upper switching pressure
3.8 ± 0.2 bar (trip pressure)
Lower switching pressure
2,8 ± 0,2 bar
Snap-action switch
Connection terminals
Lead connection: 1 or 2 leads per terminal
(Ø 0.75…2.5 mm²)
Contacts
1xNO (normally open), 1xNC (normally closed)
Utilization category
IEC 60947-5-1:
AC 15: 230 V/1 A
DC 13: 60 V/0.5 A
Maximum continuous current 10 A
Rated insulation voltage
AC: 2.5 kV/min
Table 22: General technical data