8 Technical data
Maschinenfabrik Reinhausen GmbH 2020
66
4360571/02 EN
VACUTAP
®
VM
®
Dielectric strength
AC dielectric strength between all volt-
age-carrying connections and the
grounded parts
2,500 V, 50 Hz, test duration 1 minute
AC dielectric strength between the
opened contacts
1,150 V, 50 Hz, test duration 1 minute
Table 23: Dielectric strength
8.3.2 Protective relay with several dry-reed magnetic switches
The protective relay can be supplied with several independent dry-reed mag-
netic switches. These can be designed as normally open (NO) or normally
closed (NC) contacts and are electrically isolated (see dimensional drawing
supplied).
Electrical data for normally open (NO) and normally closed (NC) dry-reed
magnetic switch
8.4 Technical data for pressure monitoring device
General technical data
Setup
Outdoor model
Ambient temperature
-40 °C…+80 °C (mechanical)
Cable gland
M25x1.5
Degree of protection
IP55 in accordance with IEC 60529 (enclosed de-
vice)
Relay actuation
Corrugated tubing with counter-pressure spring
Oil temperature
-40 °C…+100 °C
Weight
approx. 1.2 kg
Equipment
For standard insulating fluids (IEC60296 and
IEC60422)
Sealing material
(oil – air)
VITON
Permitted pressure range
(absolute pressure)
1 bar…6 bar, vacuum not permitted
Upper switching pressure
3.8 ± 0.2 bar (trip pressure)
Lower switching pressure
2,8 ± 0,2 bar
Snap-action switch
Connection terminals
Lead connection: 1 or 2 leads per terminal
(Ø 0.75…2.5 mm²)
Contacts
1xNO (normally open), 1xNC (normally closed)
Содержание VACUTAP VM I 1002
Страница 1: ...On load tap changer VACUTAP VM Operating Instructions 4360571 02 EN Selector size RC RD RDE ...
Страница 69: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 69 4360571 02 EN VACUTAP VM 9 Drawings ...
Страница 70: ......
Страница 71: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 81: ......