7 Maintenance
Maschinenfabrik Reinhausen GmbH 2020
60
4360571/02 EN
VACUTAP
®
VM
®
Perform the DC resistance measurement in various on-load tap-changer op-
erating positions. You need to distinguish here whether the measured cur-
rent is interrupted when changing operating position or not.
Status of oil compart-
ment
Without interruption in
measured current
With interruption (mea-
sured current = 0 A be-
fore change of operating
position)
Oil compartment empty
Maximum 10 A DC
Maximum 50 A DC
Oil compartment filled with
insulating fluid
Maximum 50 A DC
Maximum 50 A DC
Table 7: Maximum permitted measured currents when performing DC resistance measurement
on transformer