8 Technical data
Maschinenfabrik Reinhausen GmbH 2020
62
4360571/02 EN
VACUTAP
®
VM
®
Electrical data for VACUTAP® VM III
On-load tap-changer
VM III 650 Y
Max. rated through-current I
rm
[A]
650
Rated short-time current [kA]
6.5
Rated duration of short-circuits [s]
3
Rated peak withstand current [kA]
16.25
Max. rated step voltage U
irm
[V]
1)
3,300
Step capacity (P
StN
) [kVA]
1,625
Rated frequency [Hz]
50...60
Table 10: Electrical data for VACUTAP® VM III
1)
The maximum rated step voltage may be exceeded by 10% due to overex-
citation of the transformer if the step capacity is limited to its rated value.
Mechanical data for VACUTAP® VM I II III
Number of operating positions
Without change-over selector: maximum 18
With change-over selector: maximum 35
Number of equipped sectors
1…3
Selector sizes
RC/RD/RDE
Dimensions
See dimensional drawings
Weight
Displacement and oil volume
Table 11: Mechanical data for VACUTAP® VM I II III
8.1.2 Permissible ambient conditions
Air temperature during operation
- 25 °C…+ 50 °C
Oil temperature during operation
- 25 °C…+ 105 °C (up to + 115 °C when the transformer is in
emergency operation)
Transport temperature, storage temperature
- 40 °C…+ 50 °C
Drying temperatures
See installation and commissioning instructions, chapter "As-
sembly"
Compressive strength
See technical data TD 61 – general section
Alternative insulating liquids
Natural ester liquid (IEC 62770) on request
Synthetic ester liquid (IEC 61099) on request
Installation height of the oil conservator
See technical data TD 61 – general section
Installation height above sea level
See technical data TD 61 – general section
Table 12: Permissible ambient conditions
Содержание VACUTAP VM I 1002
Страница 1: ...On load tap changer VACUTAP VM Operating Instructions 4360571 02 EN Selector size RC RD RDE ...
Страница 69: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 69 4360571 02 EN VACUTAP VM 9 Drawings ...
Страница 70: ......
Страница 71: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 81: ......