5 Installation and commissioning
73
BA5831400-00 EN
5.7 Connecting the current transformer (winding temperature)
WARNING
Electric shock!
Dangerous high voltages may occur when a
current trans-
former
is operated with an open secondary circuit. This can
lead to death, injuries and property damage.
► Make sure that there are no dangerous electrical voltages on the CT
secondary circuit.
► Never operate a current transformer with an open secondary circuit;
short-circuit the current transformer to prevent this.
► Ground the current transformer on one side.
► Observe the information in the current-transformer operating instruc-
tions.
NOTICE
Damage to the device due to overload!
At a nominal secondary transformer current that is not 2 A, you must also
use a universal multi-ballast transformer (e.g. MESSKO MULTI-BALLAST).
Follow the corresponding operating instructions when doing so.
► Connect the universal multi-ballast transformer in accordance with the
associated operating instructions.
► The device may be operated with an overload of up to 3 A input current
for a maximum of 0.5 hours (in accordance with IEC 354).
ü
Open the cover plate.
ü
Prepare the cable.
Содержание MESSKO MT-ST Compact
Страница 25: ...3 Product description 25 BA5831400 00 EN 3 6 Nameplate Figure 9 Nameplate ...
Страница 63: ...5 Installation and commissioning 63 BA5831400 00 EN 2 Set the micro switches back to their original value ...
Страница 78: ...8 Disposal 78 BA5831400 00 EN Observe the national disposal regulations in the country of use ...
Страница 83: ...10 Appendix 83 BA5831400 00 EN 10 1 Compact pointer thermometer dimensions Figure 65 MESSKO Compact ...
Страница 84: ...10 Appendix 84 BA5831400 00 EN 10 2 Compact RM pointer thermometer dimensions Figure 66 MESSKO Compact RM ...
Страница 90: ...10 Appendix 90 BA5831400 00 EN NPT adapters optional Figure 73 NPT adapters 1 2 NPT 3 4 NPT ...
Страница 91: ......