5 Installation and commissioning
70
BA5831400-00 EN
Setting curve
The resistance value to be set depends on the nominal secondary trans-
former current and the temperature gradient of the transformer and results
from the following setting curves:
1
2
3
gr
R
0
10
20
30
K
50
4.2
5.0
6.0
7.0
8.0
9.0
10.0
2.2 A
2.1 A
2.0 A
1.9 A
1.8 A
1.7 A
1.6 A
1.5 A
I
W
[K]
[Ω]
Figure 53: Resistance setting curve
gr
Temperature gradient
R
Resistance of the heating circuit
I
W
Nominal secondary transformer
current
Example:
Nominal secondary transformer current: 1.9 A
Required gradient: 26 K
Resistance value from setting curve: 8.6 Ω