8 Control system protocol
Maschinenfabrik Reinhausen GmbH 2021
99
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
8.4.4 Holding register
Address
Name
Unit
Decimal
places
EXTERNAL CONTROL
R = read / W = write
CONTROL PRO
Others
0
Operating mode
▪ 1 = AVR AUTO
▪ 2 = AVR MANUAL
▪ 3 = EXTERNAL CONTROL
-
0
R
R
1
Tap position
-
0
R
R
2
Operations counter (MSB)
-
0
R
R
3
Operations counter (LSB)
-
0
R
R
17
Tap-change operation (-3, -2, -1, +1, +2, +3)
-
0
-
R/W
Table 18: Holding register