4.7
Fault indicators MFA
LED 1 (yellow), „
Ready
“
- Interruption in switch cable
- Operating switch defective
- Control cable defective
After switching-on command given via operating switch, no function
1
Fig. 15 | Switching-on command does
not react
LED 4 (red), „
Line interrupt
“
After switching-on command given via operating switch, „Line interrupt“
appears
4
Fig. 16 |MFA indicates „Line interrupt“
After switching-off command given via operating switch, LEDs flash
1
Fig. 17 | MFA indicates short-circuit
Display:
Possible cause:
Display:
Possible cause:
- Cable break in the 220 V circuit
- Magnet attached wrongly or not attached
- Cable or connector defective
- Magnet defective
Display:
Posible cause:
LED 1 -5 (flashing),
- Short-circuit in the cable system 220 V
- Full earth fault of the magnet
- Magnet too much power for electrical supply
2
3
4
5
www.mozelt.com
Englisch
MOZELT GmbH & Co. KG
Load lifting magnet devices
Technical Manual:
Electrical Power Supply T4002