MGate MB3000 Modbus Gateway User Manual
26
Jumpers
The DIP switches are located beneath the DIP switch panel on the side of the unit.
To add a 120
Ω
termination resistor
, set switch 3 to ON; set switch 3 to OFF (the default setting) to
disable the termination resistor.
To set the pull high/low resistors to 150 K
Ω
, set switches 1 and 2 to OFF. This is the default setting.
To set the pull high/low resistors to 1 K
Ω
, set switches 1 and 2 to ON.
Switch 4 on the port’s assigned DIP switch is reserved.
ATTENTION
Do not use the 1 K
Ω
pull high/low setting on the MGate MB3000 when using the RS-232 interface. Doing
so will degrade the RS-232 signals and reduce the effective communication distance.