MGate MB3000 Modbus Gateway User Manual
11
Jumpers
To set the pull high/low resistors to 150 K
Ω
, leave jumpers
JP3
and
JP4
open (not shorted). This is
the default setting.
To set the pull high/low resistors to 1 K
Ω
, short jumpers
JP3
and
JP4
with jumper caps.
ATTENTION
Do not use the 1 K
Ω
pull high/low setting on the MGate MB3000 when using the RS-232 interface. Doing
so will degrade the RS-232 signals and reduce the effective communication distance.