- 7 -
Pin
RS-422
4-wire RS-485
2-wire RS-485
1
GND
GND
GND
2
Rx-
Rx-
Data -
3
Rx +
Rx +
Data +
4
Tx -
Tx -
–
5
Tx +
Tx +
–
Fiber Cable
SC-Port Pinouts
SC-Port to SC-Port Cable Wiring
ST-Port Pinouts
ST-Port to ST-Port Cable Wiring
ATEX and IECEx Information
1.
Certification number:
DEMKO 10 ATEX 0917344X
IECEx UL 13.0044X
2.
Ambient range:
Model
Ambient Temp. Range
Models without suffix
“-T”
0 to 60°C
Models with suffix “T”
-40 to 85°C
3.
Certification string: Ex ec IIC T4 Gc
4.
Standards covered: EN IEC 60079-0:2018, EN IEC 60079-7: 2015
+A1:2018
5.
IEC 60079-0, Edition 7, IEC 60079-7, Edition 5.1Conditions of safe
usage:
•
The Ethernet communication devices must be mounted in a
tool-accessible IP54 enclosure in accordance with IEC/EN
60079-0 and used in an area of not more than pollution
degree 2 as defined by IEC/EN 60664-1.
•
Provisions shall be made to prevent that transient
disturbances should exceed the rated voltage by over 140%.
6.
The Terminal blocks (J1, J2) are suitable for 14 to 28 AWG
(3.31-0.08 mm
2
), with torque = 1.7 lb-in. The cross-sectional area
of the PE conductor is Sp=3.31 mm
2
. The conductor used for
grounding is 12 AWG minimum.
7.
Conductors suitable for use in an ambient temperature of 91°C
must be used for the power supply terminal.