Repair Section
61
(2) Removal of gauge manifold
1)
Crimp the pinch-off tube with a pinch-off tool.
2)
Remove the gauge manifold and the process
tube fitting. Crush the end of the pinch-off tube.
3)
Braze the end of the pinch-off tube.
4)
Ensure that a gas leak is not present at the
pinched off portion and the brazed end.
(3) Inspection of the unit after refrigerant charging
• Check the operation of the unit.
I002185
Pinch-Off Tube
Pinch-Off Tool
Process Tube Fitting
Charging Hose
To Gauge
Manifold Side
To Refrigerant
Cycle Side