Repair Section
41
7.8 Auxiliary Relay Inspection
• Check the continuity across the terminals 13
and 14, when the test button is depressed as
well as when released.
(Reference)
7.9 Full Drain Switch Inspection
• Depress the full drain switch to check for
continuity. If there is no continuity, replace the
switch.
• Normally: Continuity across 1 and 2.
• Switch Depressed: Continuity across 1 and 3.
7.10 Thermistor Inspection
• Use an ohmmeter to check the resistance
across the 2-pin connector at normal
temperature (25 °C).
Terminals
State of Reset Switch
Continuity
13-14
Depressed
Continuity
Released
No continuity
23-24
Depressed
Continuity
Released
No continuity
33-34
Depressed
Continuity
Released
No continuity
43/41-
44/42
Depressed
Continuity
Released
No continuity
Type
Specification
Characteristic
Evaporator Inlet Air
Thermistor (RTS)
5 k ohm at 25 °C
Freeze Protection Thermistor
(CTS)
5 k ohm at 25 °C
I001694
13
14
A1
A2
I001745
Full Drain Switch
Relay
Board
(CN16)
1
2
3
NC
COM
NO
C (1)
NC (2)
I001695