Parameter
Description
Output Divider:
This register is only active with standard resolution (Parameter „High
Resolution“ = 0).
The frequency generated by the converter is divided by the value set to
this register, before it appears at the output.
Setting 1 results in no division (Frequency output 1:1).
Setting 2 results in output frequency divided by 2 etc.
The maximum possible setting is 10.000 for a 1:10 000 division
It is a “must” to use the divider whenever you like to generate
frequencies lower than 62.5 Hz.
Linearization Setting
P1(x), P1(y), …,
P16(x), P16(y):
See description of the linearization function in chapter
Protocol Setting
The following register settings control the automatic cyclic transmission
of internal register values by serial interface to peripherals like printers
or displays. Please note: For cyclic transmission of a register value DIL-
switch 6 must be set to “Printer Mode” (see chapter
Serial Protocol:
Selects the serial protocol for the cyclic transmission.
0:
the string starts with the serial address of the unit (Unit
Number), followed by a space and the value of the register to be
read out. The string ends with a “Line Feed” character and a
“Carriage Return” character.
1:
the unit number is omitted, the string starts with the register
value, to allow faster transmission at shorter transmission cycles
Unit No.
Serial Protocol = 0 :
1
1
+/- X
X
X
X
X
X LF CR
Serial Protocol = 1 :
+/- X
X
X
X
X
X LF CR
Serial Timer:
Determines the cycle time in seconds for the cyclic transmission.
With a setting of e.g. 0.100 the selected register value will be transmitted
every 100 ms. The accuracy of the timer is ±500 µsec.
Register Code:
Selects the register to be transmitted cyclically. Setting of 00 selects
register code :0, setting of 01 selects register code :1 etc.