Continuation „Preselection 1 Menu“:
HYSTERESIS 1
This parameter defines the switching hysteresis of the switch-off point for preselection 1
0
No switching hysteresis
…
99999
Switching hysteresis of 99999
PULSE TIME 1 (S)
Duration of output pulse for the switching condition of preselection 1
0,000
No output pulse (static signal)
…
60,000
Pulse duration of 60 seconds
OUTPUT TARGET 1
Assignment of an output or relay for the switching condition of preselection 1.
If more than one switching condition is assigned to one output / relay, the output is set when at least one
switching condition is true
0 NO
No assignment
1 CTRL OUT 1
Switching condition assigned to “Ctrl. Out 1”
2 CTRL OUT 2
Switching condition assigned to “Ctrl. Out 2”
3 CTRL OUT 3
Switching condition assigned to “Ctrl. Out 3”
4 CTRL OUT 4
Switching condition assigned to “Ctrl. Out 4”
5 RELAY 1
Switching condition assigned to “Rel. 1”
6 RELAY 2
Switching condition assigned to “Rel. 2”
OUTPUT POLARITY 1
Polarity for the switching condition of preselection 1
0 ACTIVE HIGH
Switching condition is true
Active „HIGH“
1 ACTIVE LOW
Switching condition is true
Active „LOW“
OUTPUT LOCK 1
Latch for the switching condition of preselection 1
0 NO
No latch for preselection
1 YES
Latch for preselection (command LOCK RELEASE will clear latch)