4. Connect L1 and L2 on the MWH to L1 and L2 on the magnetic contactor using the wire size recommended
for your unit. (See table 3).
5. Connect T1 and T2 to the load side of the magnetic contactor before the over load relay heater elements as
shown below. Do not connect to the output terminals of the overload relay. Use the wire size recommended
for your unit.
6. If your system utilizes a heater off-on switch, connect it in series with normally closed auxiliary contact on the
motor starter to the terminals labeled
“SW”. Use AWG 16 wire for the circuit.
7. If your system does not utilize a heater off-on switch, connect the normally closed auxiliary contact directly to
the terminals labeled
“SW” (TB1). Note: The cover of the motor winding heater depicts the connection
diagram (See wiring diagrams below).
8. If required, connect the normally open contact from the motor overload to the overload connection as shown
on the wiring diagram.
9. Replace the cover when all connections have been completed and checked.
Wiring Diagram for units rated at
Wiring Diagram for units rated at 25 Amps
10, 50 and 80 Amps