Motor cables have no specific way of connection. The only difference is that if you 

connect the motor in one way, it will rotate in one direction, and if you connect the wires 

in the oppose it will rotate in the other direction.

In case of automatism failure or malfunction, you must detect the fail component (motor 

or central). To do that, you should test the motor directly connected to a 

24V DC

 power 

source, in order to understand if this works. 

Just disconnect the two motor cables (shaded in the image 39) which connect to the 

central and connect them directly to a 

24V DC

 battery as visible in the image 40.

DETAIL 39

07. DIAGNOSIS

CONNECT ENGINE TO 24V BATTERY

Содержание ROSSO EVO

Страница 1: ...v4 0 REV 05 2018 EN USER S AND INSTALLER S MANUAL ROSSO EVO...

Страница 2: ...ubstances in electrical and electronic equipment Applicable in countries with recycling systems This marking on the product or literature indicates that the product and electronic accessories eg Charg...

Страница 3: ...uct or other use than that for which it was designed The ELECTROCELOS S A is not responsible if safety standards were not taken into account when installing the equipment or for any deformation that m...

Страница 4: ...1200N Operating temperature 25 C a 70 C 25 C a 70 C 25 C a 70 C Thermal protection 120 C 120 C 120 C Protection grade IP20 IP20 IP20 Working frequence 70 70 70 Courtesy Light 3 minutes 3 minutes 3 min...

Страница 5: ...the side holes and create a leverage effect to release the indents fittings between the top cover and the body Then just remove the cover by lifting it To replace the cover you must first fit the bac...

Страница 6: ...no technical defects such as friction points prison that may jeopardize the automatism durability Make sure the door is in good condition to install the motor To do so raise it manually to 800mm 1600m...

Страница 7: ...Attach the rail s support plate to the lintel as visible in the image 15 In the image 16 if can be seen the distance to keep between the gate rail and support plate s upper part 125 175mm Note If you...

Страница 8: ...st be centered horizontally with the panel so that it stays aligned with the rail It should also be to fixed as higher as possible picture 24 07 Now attach the two connecting rods between the trolley...

Страница 9: ...02 Steel rail 03 Rail to ceilling s struture s fixation plate 04 Bracket for structure fixing 05 Fast rail to ceilling s struture s fixation plate 06 Trolley with unlocking system 07 Rail to lintel s...

Страница 10: ...amming the Follow Me function Enable disable condominium function Programming opening and closing courses Programming maintenance warnings Programming the automatism force level Programming transmitte...

Страница 11: ...tomatically to the programmed limits showing the message OP during the opening and CL during the closing When it finishes closing the control board will exit to the stand by mode Programming opening a...

Страница 12: ...is configured Use the or buttons to select the desired option 05 Press the M key once to save this option 06 The control board will exit to standby mode and the configuration is complete Functionality...

Страница 13: ...can be enabled or disabled via the P7 menu see pag 10 A Delete all configured transmitters 01 In stand by mode press the T key for 10sec until the display shows dl The control board has a maximum cap...

Страница 14: ...and rail motion axes The pinions at both ends of the rails as well as their supporting bearings and chain should be lubricated at least once every year 06 POST INSTALLATION STOPPER AT THE OPENING The...

Страница 15: ...irection In case of automatism failure or malfunction you must detect the fail component motor or central To do that you should test the motor directly connected to a 24V DC power source in order to u...

Страница 16: ...l an external receiver MR5SP EXCESSIVE WORKING TIME The motor stops functioning During programming does not record the course The engine is more than 1 minute in continuous operation The motor does no...

Страница 17: ...m is the fuse electrical cables or electrical current itself Check all systems 1 Give a start on the transmitter to open and check the LEDs behavior 2 If it blinks twice then the connection with the p...

Страница 18: ...TROL BOARD Pushbutton Key Selector or 230V Power Supply Fuse 2 5AL 250V Transformer IN 230V OUT 24V MOTOR m x 240W CONTROL BOARD DISPLAY BOARD Battery 24V CON1 1 Pedestrian door 2 PB 3 PE 4 GND 5 24V...

Отзывы: