12A

12

EN

Anomaly

Procedure

Behavior

Procedure II

Discovering the origin of the problem

• Motor 

doesn't 

work at all.

• Make sure you 

have power in the 

automation control 

board and if it is 

working properly.

• Still not working.

• Consult a qualified MOTORLINE 

technician.

• Motor 

doesn’t 

move

but makes

noise.

• Unlock motor and

move gate by hand 

to

check for 

mechanical

problems on the 

gate.

• Is the gate 

closed?

• Consult an experienced

gate expert.

1 • Check all motion axis and associated motion systems related with gate and operators (pins, hinges, etc.) to find out what is the problem.

• Gate moves 

easily?

• Consult a qualified

MOTORLINE technician.

• Motor 

opens

but doesn’t

close.

• Unlock motor and

move gate by hand 

to

closed position.

Lock motor(s) again

and turn off power

supply for 5 

seconds.

Reconnect it and 

send

order to open gate 

using transmitter.

• Gate opened but

didn’t close again.

1 • Check if there is any

obstacle in front of the

photocells;

2 • Check if any of the control

devices (key selector, push

button, video intercom, etc.)

of the gate are jammed and

sending permanent signal to

control unit;

3 • Consult a qualified

MOTORLINE technician.

• Motor

doesn’t 

make

complete

route.

• Unlock motor and

move gate by hand 

to

check for 

mechanical

problems on the 

gate.

• Encountered

problems?

• Consult an experienced

gate expert.

1 • Check all motion axis and associated motion systems related with gate and operators (pins, hinges, etc.) to find out what is the problem.

• Gate moves 

easily?

• Consult a qualified

MOTORLINE technician.

1 • Open control box and check 

if it has 230V/110V/24V power 

supply;

2 • Check input fuses;

3 • Disconnect motors from 

control board and test them by 

connecting directly to power 

supply in order to find out if they 

have problems (see page 8B/9).

4 • If the motors work, the 

problem is on the control board. 

Pull it out and send it to our 

MOTORLINE technical services for 

diagnosis;

5 • If the motors doesn’t work, 

remove them from installation 

site and send to our MOTORLINE 

technical services for diagnosis.

1 • Check capacitors, testing 

operator with new capacitors;

2 • If capacitors are not the 

problem, disconnect motors

from control board and test them 

by connecting directly to power 

supply in order to find out if they 

have problems (see page 8B/9).

3 • If the motors work, the 

problem is from control board. 

Pull it out and send it to our 

MOTORLINE technical services for 

diagnosis;

4 • If the motors doesn’t work, 

remove them from installation 

site and send to our MOTORLINE 

technical services for diagnosis.

1 • Check capacitors, testing with 

new capacitors;

2 • If capacitors are not the 

problem, disconnect motors from 

control board and test them by 

connecting directly to power 

supply in order to find out if they 

are faulty;

3 • If the motors doesn’t work, 

remove them from installation 

site and send to our MOTORLINE 

technical services for diagnosis.

4 • If motors work well and move 

gate at full force during the 

entire course, the problem is 

from controller. Set force using 

trimmer on the board. Make a 

new working time programming , 

giving suffient time for opening 

and closing with appropriate 

force (see manual of the 

controller in question).

5 • If this doesn’t work, remove 

control unit and send it to 

MOTORLINE technical services 

services.

NOTE:

 Setting force of the 

controller should be sufficient 

to make the gate open and close 

without stopping, but should stop 

with a little effort from a person.

In case of safety systems failure, 

the gate shall never cause 

physical damaged to obstacles 

(vehicles, people, etc.).

All MOTORLINE control boards have LEDs that 

easily allow to conclude which devices are 

with anomalies.

All safety devices LEDs (DS) in normal 

situations remain On.

All "START" circuits LEDs in normal situations 

remain Off.

If LEDs devices are not all On, there is some 

security systems malfunction (photocells, 

safety edges), etc.

If "START" circuits LEDs are turn On, there is a 

control device sending permanent signal.

A) SECURITY SYSTEMS:

1 • Close with a shunt all safety systems

on the control board (check manual of the 

control board in question).

If the automated system starts working 

normally check for the problematic device.

2 • Remove one shunt at a time until you find 

the malfunction device .

3 • Replace it for a functional device and 

check if the operator works correctly with

all the other devices. If you find another one 

defective, follow the same steps until you find 

all the problems.

B) START SYSTEMS:

1 • Disconnect all wires from START terminal 

input.

2 • If the LED turned Off, try reconnecting one 

device at a time until you find the defective 

device.

NOTE:

In case procedures described in sections A) 

and B) don’t result, remove control board and 

send to our technical services for diagnosis.

08. TROUBLESHOOTING

FINAL CONSUMERS INSTRUCTIONS

INSTRUCTIONS FOR SPECIALIZED INSTALLERS

Содержание JAG Series

Страница 1: ...V4 1 REV 04 2018 JAG EN USER S AND INSTALLER S MANUAL...

Страница 2: ...s marking on the product or literature indicates that the product andelectronicaccessories eg Charger USBcable electronicmaterial controls etc should not be disposed of as other household waste at the...

Страница 3: ...product in an emergency and provide him the manual This device can be used by children 8 year old or older and persons whose physical sensory or mental capacities are reduced or by persons without ex...

Страница 4: ...ic components in the kit Kit Package JAG specifications are as follow 01 02 03 JAG400 JAG600 Power Supply 230V 230Vac 50 60Hz 230Vac 50 60Hz 110V 110Vac 50 60Hz 110Vac 50 60Hz 24V 24Vdc 24Vdc Power 23...

Страница 5: ...tical distance from the floor to the top of the front support Set dimension A this can be any size of your choice After you set dimension A subtract 20mm to find dimension B It is very important that...

Страница 6: ...120 a 140 1295 1300 JAG 600 95 120 a 350 120 a 200 1695 1700 120 200 a 280 120 a 200 1695 1700 HORIZONTAL INSTALLATION DIMENSIONS EXTERIOR OPENING EXTERIOR INTERIOR Distance between the centers of the...

Страница 7: ...be able to stretch retract arm easily see page 03B to get the correct position for supports Install the pins removed earlier on each side with a small amount of lubricant for less friction Unlock the...

Страница 8: ...the gate to the open position 07 Loosen the screw shown in the image 24 so that it is possible to move the micro switch in the profile 08 Adjust the closure micro switch B until it makes click on the...

Страница 9: ...tant to use mechanical stoppers in the opening and closing position of the gate If not respected components of the automation may suffer efforts for which they were not prepared and as a result will b...

Страница 10: ...n the micro s If it does not operate replace with a new 24V engine and re test to ensure that all is ok To detect which are the components with problems in a 24V JAG automatism installation it is nece...

Страница 11: ...or Motor Motor Motor Black Black Gray Gray Brown Brown COM COM Power Supply Power Supply Power Supply Power Supply Power Supply Power Supply AUTOMATION AUTOMATION Ground Wire Ground Wire Ground Wire G...

Страница 12: ...cloth remove the ex cess leaving a homogeneous layer of lubri cant over the arm Place a small amount of lubricant on the holes that contains support pins Check motor supports Make sure that supports r...

Страница 13: ...board Pull it out and send it to our MOTORLINE technical services for diagnosis 4 If the motors doesn t work remove them from installation site and send to our MOTORLINE technical services for diagnos...

Отзывы: