HARDWIRE INSTRUCTIONS 011-2102-0
First make sure unit is completely disconnected from any power source and main power is completely OFF.
Begin by unscrewing the front plate which is located under the 2 x AC outlets at the front of the inverter.
You will then see the 3 connecting terminals, as illustrated below:
The recommended gauge wires are:
•
011-2102-0: Jacketed No.. 8 Gauge copper 2-wires
Some installation codes require, and we recommend use of, oil-resistant cables rated for damp or wet
locations. We would strongly recommend having this installed by a certified electrician since these wires
will have a live current, if installed improperly, can be a fire or shock hazard.
Once installed, have the wires come through the front plate by removing the middle circle of the front plate.
Once all connections are secure and properly installed, and the front plate is secured back onto the front of
inverter, you can then turn inverter back ON to test out AC connection. Make sure to test AC output from
newly installed wires with a TRUE RMS voltmeter prior to operating from the hard-wire connection.