9 / 27
Overvoltage recovery
voltage
54.40±0.5V
Recovery value of total
voltage undervoltage to
Protection value of total
voltage overvoltage
Overvoltage recovery
conditions
1. When the total voltage is lower than the
recovery point, automatically recover charging.
2. When the total voltage is lower than the
protection point and the capacity is ≤95%
(regularly charging conditions: Charging once per
day), recover charging.
Floating charge voltage
57.6±0.5V
Battery
undervoltage
protection
Undervoltage protection
voltage
41.00±0.5V
20V to
Recovery value of total
voltage undervoltage
Undervoltage recovery
voltage
45.00±0.5V
Protection value of total
voltage undervoltage
To Recovery value of total
voltage overvoltage
Undervoltage recovery
conditions
The valid charging current is detected and the
voltage is higher than the recovery point.
Battery cell
temperature
alarm
High temperature alarm of
battery cell
50±3°C
Low temperature alarm
value of battery cell to
90°C
Low temperature alarm of
battery cell
0±3°C
-40°C to
High temperature alarm
value of battery cell
No charging due
to temperature
of the battery
cell
Charging high temperature
protection
65±3°C
Recovery value of charging
high temperature To 90°C
Charging high temperature
recovery
55±3°C
Recovery value of charging
low temperature
To Protection value of
charging high temperature
Charging low temperature
-10±3°C
-40°C to