MOTOMA POWER CO., LTD
Http: // www.motoma.cn
E-mail: [email protected]
Manufacturer reserves the right to alter or amend the design, model and specification without prior notice.
12 / 27
Automatic
recovery of
over current
60S
1 S to 60S
Sustainable
voltage
100V(DC)
10S
Continuous
over current
locking
The over current event with the time interval of no more than 5min is called
continuous over current.
3 times
One to 100 times
Equilibrium
function of
battery cell
Charging equilibrium of
battery cell
Cut-in conditions: State of valid charging
current
Equilibrium cut-in voltage 3,500mV
3,000mV to 4,500 mV
Voltage difference of
equilibrium cut-in
50mV
Voltage difference value
after equilibrium To 100mV
Voltage difference after
equilibrium
30mV
10mV to
Voltage difference value
of equilibrium cut-in
Equilibrium current
80mA
Equilibrium high
temperature prohibition
50°C
Prohibition value of
equilibrium low
temperature To 70°C
Equilibrium low temperature
prohibition
0 °C
-20°C to
Prohibition value of
equilibrium high
temperature
Static equilibrium of
battery cell
Cut-in conditions: All non-discharging states
Estimate based on the voltage of the battery cell
After over voltage protection, when the rest capacity of the battery is reduced
to 95% below or meets the regular charging conditions (charging once per day),
recover charging if the voltage is lower than the over voltage protection setting
point.
Manual key
setting
In the shutdown state of BMS, press the key for 1S for startup.
In the non-standby state of BMS, press the key for 3S for shutdown.
In the non-standby state of BMS, press the key for 10S, until all LEDs lights