Sockets are not
self-locked
: tension is avaible
immediately after starting also with no plug.
WARNING
!
It is strictly forbidden to connect the group
to the public mains a/o to another source of
electric power.
At the beginning of every work, check the electric
parameters and/or the controls placed on the
front.
Make sure the unit is properly grounded (12) (where
it is assembled).
the voltmeter (N) shows the single-phase voltage
whether three or single-phase current has to be
drawn.
Connect up the machine, using proper plugs and
cables in good condition to the AC socket (15) to
draw single or three-phase power.
Using several sockets at tha same time, the maxi-
mum power possible is that indicated on the data
plate.
To draw power simultaneously, see page M1.6.
The max. continuous power of the generating set
or theload current must not be exceeded.
Nominal voltage
no-load voltage
The areas,
access
of which is forbidden to un-
qualified personel, are:
- the control switchboard (front), the exhaust of
the endothermic engine
WARNING
!
USE AS A GENERATOR
19/05/05 76440-GB
I
GB
F
TS 400 PS
TS 500 PS
M
37
REV.0-05/05
-0 +10%
-0 +10%
-0 +10%
-0 +10%
110V
230V
230V
400V
THERMOPROTECTION
If you overload the genset the thermoprotection will
automatically switch off.
lf the thermoprotection is released, disconnect all
the connected loads.
Reset the thermoprotection pressing the central
pole.
CLOSED OPEN
When reset, connect the loads again.
In case the protection should act furtherly, check: the
connections, the wires or others, and if necessary
call the Assistance Service.
AvoId to hold the central
pole of the thermoprotec-
tion pressed for a long
time.
Otherwise, in case of trouble, it will not click,
dama-
ging
the generating set.
TS ... PL VERSION
Start the machine.
The voltmeter will show the auxiliary voltage which,
for machines at 1500/1800 RPM, must. be approx.
≈
230V ± 10%.
Push upwards the lever of Ground Fault Interrupter
GROUND FAULT INTERRUPTER SWITCH (GFI)
Turn on the GFI safety-switch
(D) by pushing it upwards.
The GFI is a safety device which protects the circuit
in the event of a malfunction. In this case the switch
disconnects the three and single-phase circuit when
in any part of the electric connections a current lea-
kage of more than 30 mA occurs.
PRESS TO
RESET