The frequency, and therefore the number of motor revolutions, 

is maintained constant by the motor’s speed regulation system.

Generally, this regulator is of a mechanical type and presents 

a droop from no-load to nominal load  which is less than 5 

% (static or droop), while under static conditions precision is 

maintained within ±1%.Therefore, for generators at 50Hz the 

no-load frequency can be 52–52.5 Hz, while for generators at 

60Hz the no-load frequency can be 62.5-63Hz.

In some motors or for special requirements the speed regulator 

is electronic; in these cases, precision under static  operating 

conditions attains ±0.25%, and the frequency is maintained 

constant in operation from no-load to load (isochronal operation).

POWER FACTOR - COS 

ϕ

The power factor is a value which depends on the load’s 

electrical specifications; it indicates the ratio between the Active 

Power (kW) and Apparent Power (kVA). The apparent power is 

the total power necessary for the load, achieved from the sum 

of the active power supplied by the motor (after the alternator 

has transformed the mechanical power into electrical power), 

and the Reactive Power (kVAR) supplied by the alternator. The 

nominal value for the power factor is cos

 ϕ

 = 0,8; for different 

values comprised between 0.8 and 1 it is important during 

usage not to exceed the declared active power (kW), so as to 

not overload the electricity-generating group motor; the apparent 

power (kVA) will diminish proportionally to the increase of cos 

ϕ

.

For cos 

ϕ

 values of less than 0.8 the alternator must be 

downgraded, since at equal apparent power the alternator 

should supply a greater reactive power. For reduction 

coefficients, contact the Technical Service Department.

START-UP OF ASYNCHRONOUS MOTORS

The start-up of asynchronous motors from an electricity-

generating group can prove critical because of high start-up 

currents the asynchronous motor requires (I start-up = up to 

8 times the nominal current In.). The start-up current must not 

exceed the alternator’s admissible overload current for brief 

periods, generally in the order of 250–300% for 10–15 seconds.

To avoid a group oversize, we recommend following these 

precautionary measures:

-  in the case of a start-up of several motors, subdivide the 

motors into groups and set up their start-up at intervals of 

30–60 seconds.

-  when the operating machine coupled to the motor allows 

it, see to a start-up with reduced voltage, star point/triangle 

start-up or with autotransformer, or use a soft-start system.

In all cases, when the user circuit requires the start-up of an 

asynchronous motor, it is necessary to check that there are 

no utilities inserted into the installation, which in the case of 

a voltage droop can cause more or less serious disservices 

(opening of contact points, temporary lack of power to control 

and command systems, etc.).

SINGLE-PHASE LOADS 

Power to monophase utilities by means of three-phase 

generators requires some operating limitations.

-  In single-phase operation, the declared voltage tolerance 

can no longer be maintained by the regulator (compound 

or electronic regulator), since the system becomes highly 

unbalanced.

 The voltage variation on the phases 

not affected by the power can prove dangerous; we 

recommend sectioning the other loads eventually 

connected

.            

-  The maximum power which can be drawn between Neutral 

and Phase (start connection) is generally 1/3 of the nominal 

three-phase power; some types of alternators even allow for 

40%. Between two Phases (triangle connection) the maximum 

power cannot exceed 2/3 of the declared three-phase power.

-  In electricity-generating groups equipped with monophase 

sockets, use these sockets for connecting the loads. In other 

cases, always use the "R" phase and Neutral.

ELECTRIC PROTECTIONS

THERMAL-MAGNETIC SWITCH

The electricity-generating group is protected against short-

circuits and against overloads by a thermal-magnetic switch 

(Z2) situated upstream from the installation. Operating currents, 

both thermic and magnetic, can be fixed or adjustable in relation 

to the switch model.

+

 

In models with adjustable operating current 

do not modify

 

the settings, since doing so can compromise the installation’s 

protection or the electricity-generating group’s output characte-

ristics. For eventual variations, contact 

our Technical Service Department.

The intervention of the protection feature 

against overloads is not instantaneous, 

but follows a current overload/time 

outline; the greater the overload the 

less the intervention. Furthermore, 

keep in mind that the nominal operating 

current refers to an operating temperature of 30°C, so that 

each variation of 10°C roughly 

corresponds to a variation of 

5% on the value of nominal 

current.

In case of an intervention on 

the part of the thermal magnetic 

protection device, check that the total absorption does not 

exceed the electricity-generating group’s nominal current.

USING THE GENERATOR

26

Содержание NAKED GE 3500 HBM

Страница 1: ...genos Stromerzeuger GrupoGerador Stroomaggregaten Skupinagener toru Codice Code Code Codigo Kodezahl C digo Code K d Edizione Edition dition Edici n Ausgabe Edi o Editie Edice 07 2016 NAKED GE 3500 HB...

Страница 2: ......

Страница 3: ...13 3 INSTALLATION AND USE M2 7 INSTALLATION PAG 14 M2 6 INSTALLATION AND ADVICE PAG 15 M25 SET UP FOR OPERATION GASOLINE ENGINE PAG 19 EARTHING KIT PAG 20 M26 1 STARTING AND STOPPING HONDA GASOLINE EN...

Страница 4: ...must also given to him Do not damage it do not take parts away do not tear pages and keep it in places protected from dampness and heat You must take into account that some figures contained in it wan...

Страница 5: ...22 Rated altitude above sea level 23 Max ambient temperature 24 Dry weight kg 25 Any additional information Any of our product is labelled with CE marking attesting its conformity to appliable direct...

Страница 6: ...not respec ted damage can happen to persons or things HIGH VOLTAGE Attention High Voltage There can be parts in voltage dangerous to touch The non observance of the advice implies life danger FIRE Dan...

Страница 7: ...liquids from lungs If you suppose that vomit has entered the lungs as in case of spontaneous vomit take the subject to the hospital with the utmost urgency Inhalation In case of exposure to high conc...

Страница 8: ...trailers or site tows Never drag the machine without trailer or site tow Check for a correct assembly of the machine to the towing device Always make sure that the hook of the vehicle is suitable for...

Страница 9: ...AND USE Make sure the area above the lighting tower is free from overhead cables or other obstacles Before raising the mast extract the outriggers located at the sides of the machine Acting on the ou...

Страница 10: ...n alternator The model GE3500 is a compact diesel generating set is easily transported using a trolley The design incorporates a steel structure with engine and alternator mounted on anti vibration da...

Страница 11: ...machine is necessary to record some data Please write the requested data inside the squares to side 1 Model of machine 2 Serial number of the machine 3 Serial number of the engine 4 Name of the deale...

Страница 12: ...ndling or taking away of parts contained inside the packing or in the set In case you find damages rough handling or absence of parts envelopes manuals etc we advise you to inform immediately our Tech...

Страница 13: ...and regulations Only authorized persons involved in the transport of the machine should be in the area of movement DO NOT LOAD OTHER PARTS WHICH CAN MODIFY WEIGHT AND BARICENTER POSITION IT IS STRICTL...

Страница 14: ...13 11 14 CJ6D6010_IT M 2 7 INSTALLAZIONE INSTALLATION INSTALLATION INSTALACI N LUFTZIRKULATION INSTALA O INSTALLATIE GE 3500 HBM KBM REV 0 07 16 14...

Страница 15: ...rce ATTENTION All generating sets are equipped with a control system that is NOT influenced by standard environmental factors and is able to stop the unit in case of anomalous values in the fundamenta...

Страница 16: ...in pos sible liquid leakages hence no specific measures are needed in this regard In case of doubts concerning your genset do not hesita te to contact our technical sales office ATTENTION Engine and a...

Страница 17: ...o it by using screw anchors or rag bolts Base dimensions should exceed genset dimensions of at least 200 mm on each side Base should weigh three times static genset weight indicated on the technical d...

Страница 18: ...aluated If the duct is not appro priately insulated room temperature may increase considera bly for this reason it may be necessary to install an electro ventilator for correct air exchange a Radiator...

Страница 19: ...shown on the manual attached to the battery When battery is activated DON T add any other liquid LUBRICANT Please refer to the motor operating manual for the recommen ded viscosity To check the oil l...

Страница 20: ...ct by means of the GFI Connect the generating set to an earthing system via a cable certain efficiency using the ground terminal 12 on the machine EARTHING KIT WITH GROUND FAULT INTERRUPTER The ground...

Страница 21: ...ergency simply turn the engine switch to the OFF position Under normal conditions use the following procedure 1 stop to draw single phase current from the auxiliary sockets 2 Wait for a few minutes to...

Страница 22: ...ed with the starter off let it turn for a few minutes before drawing the load STOPPING To stop the engine in an emergency simply turn the engine switch to the OFF position Under normal conditions use...

Страница 23: ...teur F llverschluss Motor l 26 Tappo serbatoio Fuel tank cap Bouchon r servoir F llverschluss Kraftstofftank 27 Silenziatore di scarico Muffler Silencieux d chappement Auspufftopf 28 Interruttore moto...

Страница 24: ...oio Fuel tank cap Bouchon r servoir F llverschluss Kraftstofftank 27 Silenziatore di scarico Muffler Silencieux d chappement Auspufftopf 28 Comando stop Stop control Commande stop Stop Hebel 31 Tappo...

Страница 25: ...8528 1 and 3046 1 Norms and their definitions are listed in the manual s TECHNICAL SPECIFICATIONS page During the use of the electricity generating group NEVER EXCEED the power indications paying care...

Страница 26: ...ting machine coupled to the motor allows it see to a start up with reduced voltage star point triangle start up or with autotransformer or use a soft start system In all cases when the user circuit re...

Страница 27: ...ectricity generating group in combination with the EAS automatic start up panel forms a unit for distributing electrical energy within a few seconds of a power failure from the commercial electrical p...

Страница 28: ...on feature verify that the c c terminal battery connections respect the polarities the battery is not faulty or has a short circuited element the battery level is not too low with the consequent recha...

Страница 29: ...erating Manual DIESEL ENGINE The motor does not start up or starts up and then stops immediately 1 Lack of fuel in tank or fuel tap closed 2 Fuel filter clogged 3 Air leaks in fuel system 4 Battery no...

Страница 30: ...ith setting wrong or fault 1 Regulate speed to its nominal no load value 2 Check winding diodes etc on alternator See to alternator manual Repair or replace A s k f o r intervention of Service Departm...

Страница 31: ...ALS AND LABELS All warning and decals should be checked once a year and replaced if missing or unreadable STRENUOUS OPERATING CONDITIONS Under extreme operating conditions frequent stops and starts du...

Страница 32: ...th or safety respecting completely the laws and or dispositions in force in the place M 45 STORAGE AND CUST OFF REV 0 06 00 CUST OFF Have qualified personnel disassemble the machine and dispose of the...

Страница 33: ...able loads for a yearly number of hours limited at 500 h No overload is admitted Prime power PRP maximum available power for use at variable loads for a yearly illimited number of hours The average po...

Страница 34: ...13 11 14 CJ6D6010_IT M 2 7 1 DIMENSIONI DIMENSIONS DIMENSIONS DIMENSIONES ABMESSUNGEN DIMENS ES AFMETINGEN GE 3500 HBM KBM REV 0 07 16 650 490 520 34...

Страница 35: ...arity change X4 Base current diode bridge Y4 PCB control unit polarity inverter A5 Base current switch B5 Auxiliary push button ON OFF C5 Accelerator electronic control D5 Actuator E5 Pick up F5 Warni...

Страница 36: ...X G a d n o H e n i g n E 23212 S 010 Balducci F 2 Approvato Esp Data Dis Appr Modifica Denominazione Macchina Data Progetto di n Pag n 3 r p p A e t a D Approved Project Denomination Machine Modifica...

Страница 37: ...W Y Y H3 S2 BL R Y LED EXT EXT OIL AL G3 BL R ROSSO RED Engine Honda GX 270 UT2 manual recoil starter oil alert 25460 prg 25460 S 010 2 Approvato Esp Data Dis Appr Modifica Denominazione Macchina Data...

Страница 38: ...230V 16A H B Q4 C ROTOR BL BL R B BL B B B B B B B B B Y Y Y Y F F 10A Y GIALLO YELLOW R B B F A Unificato schema 6 1 0 2 5 0 7 2 16A P4 GE 4000 GE 5000 GE 3500 12A Aux 230Mx2 12DC T CJ6D6010 prg 2537...

Страница 39: ......

Страница 40: ...MOSA div della BCS S p A Viale Europa 59 20090 Cusago Milano Italy Tel 39 0290352 1 Fax 39 0290390466 www mosa it...

Отзывы: