USE AS A GENERATOR

WELDING DIGITAL CONTROL

M

37

REV.1-06/10

09/04/02  M37DSP-GB

GENERATION IN AC (ALTERNATING CURRENT)

Make certain of the efficiency of the ground connec

-

tion (12).         - See page M20 -.

Position the GFI switch to ON.

Voltage is now immediately available to the AC 

sockets.

Verify that the voltmeter displays the nominal vol

-

tage value (at no load it is close to +10% of the 

nominal value).

Connect the electric devices to be powered to the 

AC sockets, using suitable plugs and cables in good 

condition.

+

  Verify that the electrical characteristics (voltage/

frequency/power) of the device being powered 

are compatible with those of the generator.

  Low  frequency  and/or  voltage  can  irreparably 

damage some electrical devices.

Verify that the ground lead of the electrical applian

-

ce/tool to be powered is correctly connected to the 

terminal of the plug.

For double  insulation  devices  with the symbol

           , the plug’s ground terminal does not need 

to be grounded.

THERMAL PROTECTION

The monophase outputs are protected against over

-

loads by the thermal protection (59B).

When the rated current is exceeded, the protection 

intervenes to cut off the voltage to the AC socket.

+

 

Notes:

 the intervention of the thermal protection 

is not instantaneous, but reacts according

to an overcurrent/time characteristic, whereby the 

greater the overcurrent the quicker the intervention.

In  case  of  intervention  by  the  protection  device, 

verify that the total power for the loads connected 

does not exceed the declared rating and decrease 

if necessary. Disconnect the loads and wait a few 

minutes to allow the thermal 

protection to cool down.

Before resetting by pressing 

the  central  button  and  then 

connect the load again.

If the protection should intervene again, replace it 

with another one with matching intervention current 

specifications  and/or  contact  the  Service  Depart

-

ment.

+

 Note: do not forcibly hold the central button of 

the thermal protection device to prevent its inter

-

vention, as this could irreparably

 damage 

the unit’s 

alternator.

+

 Note: the three phase output does not require any 

protection against overcurrents, since it uses a 

self-protecting asynchronous type alternator.

GROUND FAULT INTERRUPTOR SWITCH

The high-sensitivity ground fault interruptor switch 

[G.F.I.] (30mA) (D), guarantees protection against 

indirect contacts due to faulty ground currents .

When the G.F.I.  switch picks up a faulty ground 

current that is higher than 30mA, it inter

-

venes by immediately cutting off voltage 

to the AC sockets.

In case of intervention by this protection 

device, reset the G.F.I. switch by moving 

the lever to the ON position. In case of 

another intervention, verify that there are no faults 

in the tools connected, or replace the G.F.I. switch 

with another one of matching specifications and/or 

contact the Service Department.

+

 

Notes:

  Verify the operation of the G.F.I. switch 

at least once a month by pressing the TEST button.

The generator must be running and the G.F.I. lever 

in the ON position.

SIMULTANEOUS USE

The  welder’s  alternator  permits  the  simultaneous 

use of auxiliary power and welding current. The auxi

-

liary power available to the AC plugs (15) diminishes 

as the welding current drawn increases.

The  table  on  page  M1.6  TECHNICAL  SPECIFI

-

CATIONS  shows  the  amount  of  auxiliary  power 

available as the welding current varies.

COMBINED USE

The  output  available  from  the  various  auxiliary 

power sockets is limited, not only by the declared 

output of the unit but also by the capacity of each 

individual socket.

PUSH TO

RESET

WARNING

It is strictly forbidden to connect the group to 

the public mains and/or to any other source 

of electric power.

!

Содержание DSP 500 PS

Страница 1: ...digo Edizione Edition dition Edici n Ausgabe Edi o 785109003 Motosaldatrice EngineDrivenWelder Motosoudeuse Motosoldadoras Schwei aggregat Motosoldadora DSP 500 PS 02 2016 USE AND MAINTENANCE MANUAL T...

Страница 2: ......

Страница 3: ...kHz chopper system while the regulation board is implemented with digital technology From a mechanical viewpoint the machine is composed of a basement which incorporates the tank and a roll bar which...

Страница 4: ...INSTALLATION M 2 7 1 DIMENSIONS M 3 UNPACKING M 4 TRANSPORT AND DISPLACEMENTS COVERED UNITS M 6 2 ASSEMBLY CTL M 20 PREPARING THE UNIT M 21 START UP M 22 SHUTTING DOWN THE MOTOR M 39 13 ENGINE PROTECT...

Страница 5: ...matter In no case MOSA division of B C S S p A will be held responsible for any damaga direct or indirect in relation with the use of the given information MOSA division of B C S S p A does not take...

Страница 6: ...ke parts away do not tear pages and keep it in places protected from dampness and heat You must take into account that some figures contained in it want only to identify the described parts and theref...

Страница 7: ...cluded in any machine standard equipment Here below the adopted symbol CE marking is clearly readable and unerasable and it can be either part of the data plate Furthermore on each model it is shown t...

Страница 8: ...ive humidity altitude 100 m above sea level It s admitted overload of 10 each hour every 12 h In an approximative way one reduces of 1 every 100 m altitude and of 2 5 for every 5 C above 25 C ACOUSTIC...

Страница 9: ...erload of 10 each hour every 12 h In an approximative way one reduces of 1 every 100 m altitude and of 2 5 for every 5 C above 25 C ACOUSTIC POWER LEVEL ATTENTION The concrete risk due to the machine...

Страница 10: ...DING Welding current 450A 60 400A 100 Welding voltage 16 40V WELDING CURRENT A 0 100 150 300 400 500 AUXILIARY POWER 3 PHASE kW 16 14 12 6 3 0 STATIC CHARACTERISTIC SIMULTANEOUS UTILIZATION FACTORS In...

Страница 11: ...r whatever event which may cause serious injuries or death predispose the first aid in accordance with the ruling labour accident standards or of local instructions FIRE PREVENTION In case the working...

Страница 12: ...ersons Use only with safety clothing It is compulsory to use the personal protection means given in equip ment Use only with safety clothing It is compulsory to use the personal protection means given...

Страница 13: ...area is safe before starting any welding operation Do not touch any bare wires leads or contacts as they may be live and there is danger of electric shock which can cause death or serious burns The el...

Страница 14: ...a dangerous increase of the temperature Make sure that the machine does not move during the work block it possibly with tools and or devices made to this purpose Maximum leaning of the machine in cas...

Страница 15: ...Installazione Installation Installation Luftzirkulation 21 09 07 78510 IT M 2 7 REV 0 09 07...

Страница 16: ...Dimensioni Dimensions Installation Abmessungen 21 09 07 78510 IT M 2 7 1 REV 0 09 07...

Страница 17: ...rough handling or taking away of parts contained inside the packing or in the set In case you find damages rough handling or absence of parts envelopes manuals etc we advise you to inform immediately...

Страница 18: ...s and regulations Only authorized persons involved in the transport of the machine should be in the area of movement DO NOT LOAD OTHER PARTS WHICH CAN MODIFY WEIGHT AND BARICENTER POSITION IT IS STRIC...

Страница 19: ...o as to let the foot sprag 4S go through 4 Introduce into the jaw 3 the upper part 4S of the foot and block momentaneously with the lever 4L the whole foot 6 Assemble on the machine the towbar 5 compl...

Страница 20: ...case of models with war ning light check the state of the battery by means of the indicator placed in the upper part Green colour battery OK Black colour battery to be recharged White colour battery...

Страница 21: ...N A qualified electrician should carry out electrical con nections according to the norms in force Electrical connections The electrical connection to the User system is a very important operation saf...

Страница 22: ...imer lamp is used the yellow PREHEAT LED co mes on for the set time of the imposed settings C As soon as the green ENGINE RUNNING LED starts to flash actuate the key switch in a clockwise direction mo...

Страница 23: ...xiliary generation dividing the loads or opening the electri cal protection interrupter 3 Let the engine run with no load for a few minutes 4 Turn the start key on the EP7 to the OFF position OFF ON S...

Страница 24: ...instruments PCB and Led V R D PCB Welding selector mode Welding current regulator Polarity inverter control Remote control socket Prise de soudage Prise de soudage Prises de courant en c a Protection...

Страница 25: ...qualified personnel is prohibited in proximity of these areas the control panel front end the engine exhaust fumes the welding process Make sure that the ground clamp whose cable must be connected to...

Страница 26: ...age adjusting knob to the minimum setting SETTING THE WELDING PROCESS 11 10 04 M33_WDC_GB CV CC STAND BY CONTACT STARTING REMOTE CONTROL 70 20 25 40 100 WELDING DIGITAL CONTROL 130 160 190 220 250 280...

Страница 27: ...Digital Control features 3 protections for the control and chopper 11 10 04 M33_WDC_GB 1 ON LED blinking When the engine of the welder is started the control unit automatically goes to the stand by mo...

Страница 28: ...low mentioned table WARNING A electric ground B C 5 V d c D E F 5 V d c G H welding ground I 44 48V a c J 44 48V a c DESCRIPTION To potentiometer RC1 terminal a To potentiometer RC1 central b To poten...

Страница 29: ...should intervene again replace it with another one with matching intervention current specifications and or contact the Service Depart ment Note do not forcibly hold the central button of the thermal...

Страница 30: ...nctional and automati cally excludes the front panel regulation The remote control can also be connected to the connector on the wire feeder front panel but in this case it is ne cessary to switch the...

Страница 31: ...ontrol connector 8 it is functional and automati cally excludes the front panel regulation The remote control can also be connected to the connector on the wire feeder front panel but in this case it...

Страница 32: ...fuel condition occurs This LED illuminates continuously to indicate a shut down if the switch has been closed for more than 5 minutes TEMPERATURE red LED This LED illuminates when an High Temperature...

Страница 33: ...ays on 1 WDC defective 2 Chopper defective 3 Current sensor defective 1 Switch off the machine and start it up again if the LED remains off try to weld verifying that the welding is regular if the LED...

Страница 34: ...outputs on the generator except for those on the con densers and re start machine check for voltage on condensers MOTOR P1 The engine does not start or stops immediately after startup 1 Low battery vo...

Страница 35: ...tiometer of the WDC works correctly perform the following test 1 Start the welding machine and let it run at nominal r p m 2 Connect a multimeter set for VDC mea surement between pins 1 GND and 12 of...

Страница 36: ...SP EP5 ES_GB DRAWING 5 DRAWING 4 Put the knob on RC1 at minimum max put one ohmmeter from pin A B and measure the resistance Knob Resistance Minimum Max 50 100 4 5 4 7 K P1 Supply connector P2 Chopper...

Страница 37: ...O NOT USE COMPRESSED AIR DECALS AND LABELS All warning and decals should be checked once a year and replaced if missing or unreadable STRENUOUS OPERATING CONDITIONS Under extreme operating conditions...

Страница 38: ...n the covers and all the other parts of the machine carefully Protect the machine with a plastic hood and store it in o dry place DIESEL ENGINE For short periods of time it is advisable about every 10...

Страница 39: ...he various components of the machine must be made accordingly to rules in force of law a o local rules Particular attention must be paid when getting rid of lubricating oils battery electrolyte and in...

Страница 40: ...ground clamp Special for steels run on pipes with R max 55 kg mm2 Weld in all position volatile slag ELECTRODES IDENTIFICATION ACCORDING TO A W S STANDARDS E X X Y Z 2 digits type of coating and elect...

Страница 41: ...ansformer 230 48V W4 Diode bridge polarity change X4 Base current diode bridge Y4 PCB control unit polarity inverter A5 Base current switch B5 Auxiliary push button ON OFF C5 Accelerator electronic co...

Страница 42: ...21 09 07 78510 IT M 61 1 REV 0 09 07 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 43: ...21 09 07 78510 IT Schema elettrico Stromlaufplan Electric diagram 400T230M110M M 61 2 REV 0 09 07...

Страница 44: ...21 09 07 78510 IT 400T230M48M M 61 3 REV 0 09 07 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 45: ...21 09 07 78510 IT 400T230Mx3 M 61 4 REV 0 02 16 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 46: ...21 09 07 78510 IT 400T230M127M 60Hz M 61 5 REV 0 02 16 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 47: ...21 09 07 78510 IT 400T230M48M M 61 6 REV 2 12 12 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 48: ...21 09 07 78510 IT 400T230M110M M 61 7 REV 2 06 13 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 49: ...21 09 07 78510 IT 400T230M48M M 61 8 REV 2 06 13 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 50: ...21 09 07 78510 IT 400T230M48M M 61 9 REV 1 10 09 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 51: ...21 09 07 78510 IT 400T230M110M M 61 10 REV 1 10 09 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico Esquema el trico...

Страница 52: ......

Страница 53: ......

Страница 54: ...MOSA div della BCS S p A Viale Europa 59 20090 Cusago Milano Italy Tel 39 0290352 1 Fax 39 0290390466 www mosa it...

Отзывы: