The frequency, and therefore the number of motor revolutions, 

is maintained constant by the motor’s speed regulation system.

Generally, this regulator is of a mechanical type and presents 

a droop from no-load to nominal load  which is less than 5 

% (static or droop), while under static conditions precision is 

maintained within ±1%.Therefore, for generators at 50Hz the 

no-load frequency can be 52–52.5 Hz, while for generators at 

60Hz the no-load frequency can be 62.5-63Hz.

In some motors or for special requirements the speed regulator 

is electronic; in these cases, precision under static  operating 

conditions attains ±0.25%, and the frequency is maintained 

constant in operation from no-load to load (isochronal operation).

POWER FACTOR - COS 

ϕ

The power factor is a value which depends on the load’s 

electrical specifications; it indicates the ratio between the Active 

Power (kW) and Apparent Power (kVA). The apparent power is 

the total power necessary for the load, achieved from the sum 

of the active power supplied by the motor (after the alternator 

has transformed the mechanical power into electrical power), 

and the Reactive Power (kVAR) supplied by the alternator. The 

nominal value for the power factor is cos

 ϕ

 = 0,8; for different 

values comprised between 0.8 and 1 it is important during 

usage not to exceed the declared active power (kW), so as to 

not overload the electricity-generating group motor; the apparent 

power (kVA) will diminish proportionally to the increase of cos 

ϕ

.

For cos 

ϕ

 values of less than 0.8 the alternator must be 

downgraded, since at equal apparent power the alternator 

should supply a greater reactive power. For reduction 

coefficients, contact the Technical Service Department.

START-UP OF ASYNCHRONOUS MOTORS

The start-up of asynchronous motors from an electricity-

generating group can prove critical because of high start-up 

currents the asynchronous motor requires (I start-up = up to 

8 times the nominal current In.). The start-up current must not 

exceed the alternator’s admissible overload current for brief 

periods, generally in the order of 250–300% for 10–15 seconds.

To avoid a group oversize, we recommend following these 

precautionary measures:

-  in the case of a start-up of several motors, subdivide the 

motors into groups and set up their start-up at intervals of 

30–60 seconds.

-  when the operating machine coupled to the motor allows 

it, see to a start-up with reduced voltage, star point/triangle 

start-up or with autotransformer, or use a soft-start system.

In all cases, when the user circuit requires the start-up of an 

asynchronous motor, it is necessary to check that there are 

no utilities inserted into the installation, which in the case of 

a voltage droop can cause more or less serious disservices 

(opening of contact points, temporary lack of power to control 

and command systems, etc.).

SINGLE-PHASE LOADS 

Power to monophase utilities by means of three-phase 

generators requires some operating limitations.

-  In single-phase operation, the declared voltage tolerance 

can no longer be maintained by the regulator (compound 

or electronic regulator), since the system becomes highly 

unbalanced.

 The voltage variation on the phases 

not affected by the power can prove dangerous; we 

recommend sectioning the other loads eventually 

connected

.            

-  The maximum power which can be drawn between Neutral 

and Phase (start connection) is generally 1/3 of the nominal 

three-phase power; some types of alternators even allow for 

40%. Between two Phases (triangle connection) the maximum 

power cannot exceed 2/3 of the declared three-phase power.

-  In electricity-generating groups equipped with monophase 

sockets, use these sockets for connecting the loads. In other 

cases, always use the "R" phase and Neutral.

ELECTRIC PROTECTIONS

THERMAL-MAGNETIC SWITCH

The electricity-generating group is protected against short-

circuits and against overloads by a thermal-magnetic switch 

(Z2) situated upstream from the installation. Operating currents, 

both thermic and magnetic, can be fixed or adjustable in relation 

to the switch model.

+

 

In models with adjustable operating current 

do not modify

 

the settings, since doing so can compromise the installation’s 

protection or the electricity-generating group’s output characte-

ristics. For eventual variations, contact 

our Technical Service Department.

The intervention of the protection feature 

against overloads is not instantaneous, 

but follows a current overload/time 

outline; the greater the overload the 

less the intervention. Furthermore, 

keep in mind that the nominal operating 

current refers to an operating temperature of 30°C, so that 

each variation of 10°C roughly 

corresponds to a variation of 

5% on the value of nominal 

current.

In case of an intervention on 

the part of the thermal magnetic 

protection device, check that the total absorption does not 

exceed the electricity-generating group’s nominal current.

UsE As gEnErAtor

25

Содержание CD4R90119003

Страница 1: ...erador Stroomaggregaten Skupinagener toru CD4R90119003 Codice Code Code Codigo Kodezahl C digo Code K d Edizione Edition dition Edici n Ausgabe Edi o Editie Edice OPEN FRAME GE 10000 HZDM STAGE V GE 1...

Страница 2: ......

Страница 3: ...RT AND HANDLING M3 MACHINE UNPACKING PAG 12 M4 1 TRANSPORT AND HANDLING COVERED UNITS PAG 13 3 INSTALLATION AND USE M2 7 INSTALLATION PAG 14 M2 6 INSTALLATION ADVICES PAG 15 M20 SET UP FOR OPERATION D...

Страница 4: ...must also given to him Do not damage it do not take parts away do not tear pages and keep it in places protected from dampness and heat You must take into account that some figures contained in it wan...

Страница 5: ...22 Rated altitude above sea level 23 Max ambient temperature 24 Dry weight kg 25 Any additional information Any of our product is labelled with CE marking attesting its conformity to appliable direct...

Страница 6: ...amage can happen to persons or things HIGH VOLTAGE Attention High Voltage There can be parts in voltage dangerous to touch The non observance of the advice implies life danger FIRE Danger of flame or...

Страница 7: ...octor Suction of liquids from lungs If you suppose that vomit has entered the lungs as in case of spontaneous vomit take the subject to the hospital with the utmost urgency Inhalation In case of expos...

Страница 8: ...o di traino previsto Verificare il corretto assemblaggio della macchina al dispo sitivo di traino Verificare sempre che il gancio del veicolo sia adeguato al traino della massa totale del carrello Non...

Страница 9: ...ione causa un grave pericolo di ribaltamento o instabilit durante il funzionamento e durante la movimentazione con carrelli di traino In caso di necessit contattare il servizio di assistenza tecnica P...

Страница 10: ...lso eliminate sounds which would produce noise The unit has a protective closed frame which protects it against unintentional impacts during the handling and or transport the front panel is completely...

Страница 11: ...machine is necessary to record some data Please write the requested data inside the squares to side 1 Model of machine 2 Serial number of the machine 3 Serial number of the engine 4 Name of the deale...

Страница 12: ...ndling or taking away of parts contained inside the packing or in the set In case you find damages rough handling or absence of parts envelopes manuals etc we advise you to inform immediately our Tech...

Страница 13: ...and regulations Only authorized persons involved in the transport of the machine should be in the area of movement DO NOT LOAD OTHER PARTS WHICH CAN MODIFY WEIGHT AND BARICENTER POSITION IT IS STRICT...

Страница 14: ...05 12 19 CD4R9011_IT M 2 7 INSTALLAZIONE INSTALLATION INSTALLATION INSTALACI N LUFTZIRKULATION INSTALA O INSTALLATIE REV 1 03 20 M1 4 M1 4...

Страница 15: ...force ATTENTION All generating sets are equipped with a control system that is NOT influenced by standard environmental factors and is able to stop the unit in case of anomalous values in the fundamen...

Страница 16: ...tain pos sible liquid leakages hence no specific measures are needed in this regard In case of doubts concerning your genset do not hesita te to contact our technical sales office ATTENTION Engine and...

Страница 17: ...to it by using screw anchors or rag bolts Base dimensions should exceed genset dimensions of at least 200 mm on each side Base should weigh three times static genset weight indicated on the technical...

Страница 18: ...e evaluated If the duct is not appro priately insulated room temperature may increase considera bly for this reason it may be necessary to install an electro ventilator for correct air exchange a Radi...

Страница 19: ...il filling and level ispections must be carried out with the engine on a flat surface 1 Remove oil filler cap 24 2 Pour the oil in and reassemble oil cap 3 Check the oil level using the dipstick 23 th...

Страница 20: ...by means of the GFI Connect the generating set to an earthing system via a cable certain efficiency using the ground terminal 12 on the machine Earthing WITH GROUND FAULT INTERRUPTER The grounding co...

Страница 21: ...t low temperatures The motor will normally start up without problems down to temperatures of 10 C For start up and use at lower temperatures please see the engine manual or turn to our Technical Assis...

Страница 22: ...e sockets 15 A C socket AUX sockets for load connection 12 Earth terminal Ground connection point for gen set Z6 Digital multifunction meter GE voltage VAC GE Hz Frequency Total hour counter Resettabl...

Страница 23: ...8528 1 and 3046 1 Norms and their definitions are listed in the manual s TECHNICAL SPECIFICATIONS page During the use of the electricity generating group NEVER EXCEED the power indications paying car...

Страница 24: ...ating machine coupled to the motor allows it see to a start up with reduced voltage star point triangle start up or with autotransformer or use a soft start system In all cases when the user circuit r...

Страница 25: ...lectricity generating group in combination with the EAS automatic start up panel forms a unit for distributing electrical energy within a few seconds of a power failure from the commercial electrical...

Страница 26: ...er clogged 2 Overload 3 Injectors defective Injection pump requires calibra tion 1 Clean or replace 2 Check the load connected and diminish 3 Ask for intervention of Service Department White smoke 1 O...

Страница 27: ...ith setting wrong or fault 1 Regulate speed to its nominal no load value 2 Check winding diodes etc on alternator See to alternator manual Repair or replace A s k f o r intervention of Service Departm...

Страница 28: ...ALS AND LABELS All warning and decals should be checked once a year and replaced if missing or unreadable STRENUOUS OPERATING CONDITIONS Under extreme operating conditions frequent stops and starts du...

Страница 29: ...uested number of hours has not been attained EVERY WEEK EVERY MONTH AND OR AFTER INTERVENTION ON LOAD EVERY YEAR 1 TEST orAUTOMATIC TEST cycle to keep the generating set constantly operative NO LOAD X...

Страница 30: ...d or dispositions in force in the place M 45 STORAGE and disassEmble REV 0 06 00 DISASSEMBLE Have qualified personnel disassemble the machine and dispose of the parts including the oil fuel etc in a c...

Страница 31: ...urs limited at 500 h No overload is admitted Prime power PRP maximum available power for use at variable loads for a yearly illimited number of hours The average power to be taken during a period of 2...

Страница 32: ...05 12 19 CD4R9011_IT M 2 7 1 DIMENSIONI DIMENSIONS DIMENSIONS DIMENSIONES ABMESSUNGEN DIMENS ES AFMETINGEN REV 1 03 20 610 665 715 1005 210 840 925 425 1430 645...

Страница 33: ...11 01 01 Note NOTE 34...

Страница 34: ...11 01 01 Note NOTE 34...

Страница 35: ......

Страница 36: ...MOSA div della BCS S p A Viale Europa 59 20090 Cusago Milano Italy Tel 39 0290352 1 Fax 39 0290390466 www mosa it...

Отзывы: