background image

4

Morrison Bros. Co.  ‑  Dubuque, IA  ‑  800‑553‑4840

1218CT0112 PP     rev 04‑14‑2022

!

!

Installation

WARNINGS

•  Any modification of this unit beyond what is outlined in this instruction will void product warranty. 

•  For your safety, it is important to follow local, state, federal and/or OSHA rules that apply to working inside, above, 

or around the storage tank and piping area. Use all personal protective equipment required for working in the specific 

environment.

• 

Install in accordance with all applicable local, state, and federal regulations and codes.

• 

In the event of malfunction, remove from service immediately and contact Morrison Bros. Customer Service.

Power Coverter Module

Mounting

1. The Power Converter Module should be installed 

directly to the bottom of the 1218C Console using 

the H050-TB conduit hub provided in the kit to 

secure the module in place. This module should be 

installed in one of the 1/2-inch conduit openings, 

shown in Figure 2.

IMPORTANT NOTE: Only the 1218CT power 

and communications conductors are to be routed 

through the module. Use a junction tee above the 

module to divert all other conductors (i.e., AC 

power, ethernet, and relay outputs). If a junction 

tee is used, the 4 conductors included in the kit 

may be too short for installation and may need to 

be replaced.

2. Ensure the conduit body cover is facing outwards 

when completing the installation, this is important for later steps.

Wiring

1218C Console Preparation Steps

WARNING

•  Shut off the AC power to the 1218C Console at the breaker before proceeding with wiring. Failure to do so may result in 

injury or death. 

1. Open the front cover of the 1218C Console by releasing the two cover latches and swinging the cover open. 

2. Remove and retain the two screws holding the shield for the Facilities section in place. 

3. Remove and retain the shield. 

1218C Power Converter Module Preparation Steps

1. Loosen the two screws on the conduit body and remove and retain the conduit body cover, along with the screws. 

2. Take the AC/DC converter out of the conduit body and remove the packaging. 

Figure 2: 1/2-inch conduit openings

Содержание 1218CT

Страница 1: ...include all electrical components and housings required to power the 1218CT Communication Module using the same power source already installed for the 1218C Console The 1218CT is capable of receiving...

Страница 2: ...8CT Power Converter Module along with assembly components to be used for installation Both modules are intended to be installed in an indoor or outdoor non hazardous location Figure 1 Fuel Management...

Страница 3: ...Note Shielded 3 conductor cable required not supplied 18 24 AWG conductor recommended Do not use twisted pair cable Input Voltage 5 VDC from Power Converter Module TLS Protocol Supported Commands In...

Страница 4: ...ORTANT NOTE Only the 1218CT power and communications conductors are to be routed through the module Use a junction tee above the module to divert all other conductors i e AC power ethernet and relay o...

Страница 5: ...6 Next strip the 8 inch wire approximately 11mm 1 2 inch Flip the third lever open insert the stripped wire into the connecter then close the lever ensuring the wire is secured properly 7 Back at the...

Страница 6: ...nt opening in the middle of the conduit body as shown in Figure 6 17 Cut the orange and brown twisted pairs leaving approximately 3 4 inches and strip each pair 5mm 1 4 inch 18 Lead both of the 8 inch...

Страница 7: ...lows the front cover to be carefully removed NOTE The corner screws that hold the front cover in place are captive screws and are not intended to be removed from the front cover Wiring Steps Figure 8...

Страница 8: ...and the white blue wire connected to pin 4 The drain wire should be connected to pin 4 along with the white blue wire Figure 10 1218CT Communication Module Board Postion Description Color 1 Data A Gre...

Страница 9: ...e GND terminal Position Color 1 Vo 5V Orange and White Orange 2 Vo Ground Brown and White Brown Description J1 Pin Assignments Figure 13 J1 Pin Assignments Table Configuration 1218 Console No configur...

Страница 10: ...Communication between the Communication Module and the FMS will be initiated by the FMS The FMS will send a command to the Communication Module then it will reply with data based on the command that...

Страница 11: ...he LEDs on the Communication Module if the Red LED is blinking this confirms there is a communication issue Refer to step 1 in this guide 2 If Red LED is not blinking check the wiring of the J3 connec...

Страница 12: ...g for the respective tank Starting date time and ending date time Starting volume and ending volume Starting height and ending height Note The 1218CT Communication Module will keep this log stored in...