Maintenance

WARNINGS

•  Any modification of this unit beyond what is outlined in this instruction will void product warranty. 

•  For your safety, it is important to follow local, state, federal and/or OSHA rules that apply to working inside, above, 

or around the storage tank and piping area. Use all personal protective equipment required for working in the specific 

environment.

• 

Install in accordance with all applicable local, state, and federal regulations and codes.

• 

This device is intended to be used as an auxiliary warning to the operator of an abnormal condition of the system, 

such as a possible overfill situation and should not be the only system in place to prevent an unwanted condition, such 

as preventing a tank from overfilling. It is the sole responsibility of the operator to continuously prevent any spillage 

regardless of the situation.

• 

In the event of malfunction, remove from service immediately and contact Morrison Bros. Customer Service.

The Communication Module and Power Converter Module do not require routine maintenance after the installation 

is completed.  If either of these modules require maintenance due to a operational related issue, please follow the 

troubleshooting guide below. 

Reference 

Number

Problem

Cause

Steps

Solution

1

Ensure that the Modbus feature on the 1218C is disabled.

2

Check the wiring on connector J4 on the 1218C and connector J2 on 

the Communication Module. Refer to the Communication Module 

wiring section beginning on page 7. 

3

If the Red LED continues to blink, contact customer service. 

1

Check the LEDs on the Communication Module, if the Red LED is 

blinking this confirms there is a communication issue. Refer to step 

1 in this guide.

2

If Red LED is not blinking, check the wiring of the J3 connector on 

the Communication Module, ensure that the RX and TX are in the 

correct position with respect to the FMS. Refer to the 

Commmunication Module wiring section on page 7.

3

If the Red LED is not blinking and this problem persists, contact 

customer service.

1

Check the wiring of the J3 connector on the Communication 

Module, ensure that the RX and TX are in the correct position with 

respect to the FMS. Refer to the Commmunication Module wiring 

section on page 7.

2

Refer to the troubleshooting guide for the FMS system that is being 

used.

1

Check the 1218C to see if this has power. If this is not powered the 

Communication Module will not have power. 

2

If 1218C has power unscrew the front panel of the Power Converter 

Module, if the LED is not illuminated on the AC/DC converter it is 

not receiving power or has malfunctioned. Refer back to the Power 

Converter Module wiring steps on page 4.

3

If AC/DC converter still does not have power, contact customer 

service. 

4

If AC/DC converter does have power and the Communication 

Module does not, refer back to the Communication Module wiring 

instructions starting on page 7. 

5

After checking the wiring if the Green LEDs on the Communication 

Module are still not illuminated, contact customer service. 

Troubleshooting Guide

This indicates that the 

Communication Module is not 

receiving any data from the 1218C

Red LED on Communication 

Module is blinking.

1

No new data is being communicated 

between the 1218C and the 

Communication Module.

Tank data read from the FMS is 

incorrect.

2

3

FMS not receiving reports

Communication error 

Green LEDs not illuminated

Power error

4

Содержание 1218CT

Страница 1: ...include all electrical components and housings required to power the 1218CT Communication Module using the same power source already installed for the 1218C Console The 1218CT is capable of receiving...

Страница 2: ...8CT Power Converter Module along with assembly components to be used for installation Both modules are intended to be installed in an indoor or outdoor non hazardous location Figure 1 Fuel Management...

Страница 3: ...Note Shielded 3 conductor cable required not supplied 18 24 AWG conductor recommended Do not use twisted pair cable Input Voltage 5 VDC from Power Converter Module TLS Protocol Supported Commands In...

Страница 4: ...ORTANT NOTE Only the 1218CT power and communications conductors are to be routed through the module Use a junction tee above the module to divert all other conductors i e AC power ethernet and relay o...

Страница 5: ...6 Next strip the 8 inch wire approximately 11mm 1 2 inch Flip the third lever open insert the stripped wire into the connecter then close the lever ensuring the wire is secured properly 7 Back at the...

Страница 6: ...nt opening in the middle of the conduit body as shown in Figure 6 17 Cut the orange and brown twisted pairs leaving approximately 3 4 inches and strip each pair 5mm 1 4 inch 18 Lead both of the 8 inch...

Страница 7: ...lows the front cover to be carefully removed NOTE The corner screws that hold the front cover in place are captive screws and are not intended to be removed from the front cover Wiring Steps Figure 8...

Страница 8: ...and the white blue wire connected to pin 4 The drain wire should be connected to pin 4 along with the white blue wire Figure 10 1218CT Communication Module Board Postion Description Color 1 Data A Gre...

Страница 9: ...e GND terminal Position Color 1 Vo 5V Orange and White Orange 2 Vo Ground Brown and White Brown Description J1 Pin Assignments Figure 13 J1 Pin Assignments Table Configuration 1218 Console No configur...

Страница 10: ...Communication between the Communication Module and the FMS will be initiated by the FMS The FMS will send a command to the Communication Module then it will reply with data based on the command that...

Страница 11: ...he LEDs on the Communication Module if the Red LED is blinking this confirms there is a communication issue Refer to step 1 in this guide 2 If Red LED is not blinking check the wiring of the J3 connec...

Страница 12: ...g for the respective tank Starting date time and ending date time Starting volume and ending volume Starting height and ending height Note The 1218CT Communication Module will keep this log stored in...

Отзывы: