Morrison Bros. Co.  ‑  Dubuque, IA  ‑  800‑553‑4840

1218CT0112 PP     rev 04‑14‑2022

1218CT Fuel Management System Translator Kit

Installation, Operation, and Maintenance Instructions

The 1218CT Fuel Management System Translator Kit is designed as an add-on to the 1218C Electronic Tank Gauge (also 

referred to as the 1218C Console), providing an interface between the 1218C Console and any fuel management system 

(FMS) that utilizes TLS protocol. This kit will include all electrical components and housings required to power the 1218CT 

Communication Module using the same power source already installed for the 1218C Console. The 1218CT is capable of 

receiving commands from any FMS communicating with TLS protocol and responding with live or historic data from the 

1218C Console in real time. 

Failure to follow any or all of the warnings and instructions in this document could result in a hazardous liquid spill, 

which could result in property damage, environmental contamination, fire, explosion, serious injury or death.

Contents

Specifications

 ......................................................................................................................................................... 2

Installation

 ............................................................................................................................................................. 4

Operation

 ............................................................................................................................................................... 9

Maintenance

 ........................................................................................................................................................ 11

Appendix A

 .......................................................................................................................................................... 12

!

Содержание 1218CT

Страница 1: ...include all electrical components and housings required to power the 1218CT Communication Module using the same power source already installed for the 1218C Console The 1218CT is capable of receiving...

Страница 2: ...8CT Power Converter Module along with assembly components to be used for installation Both modules are intended to be installed in an indoor or outdoor non hazardous location Figure 1 Fuel Management...

Страница 3: ...Note Shielded 3 conductor cable required not supplied 18 24 AWG conductor recommended Do not use twisted pair cable Input Voltage 5 VDC from Power Converter Module TLS Protocol Supported Commands In...

Страница 4: ...ORTANT NOTE Only the 1218CT power and communications conductors are to be routed through the module Use a junction tee above the module to divert all other conductors i e AC power ethernet and relay o...

Страница 5: ...6 Next strip the 8 inch wire approximately 11mm 1 2 inch Flip the third lever open insert the stripped wire into the connecter then close the lever ensuring the wire is secured properly 7 Back at the...

Страница 6: ...nt opening in the middle of the conduit body as shown in Figure 6 17 Cut the orange and brown twisted pairs leaving approximately 3 4 inches and strip each pair 5mm 1 4 inch 18 Lead both of the 8 inch...

Страница 7: ...lows the front cover to be carefully removed NOTE The corner screws that hold the front cover in place are captive screws and are not intended to be removed from the front cover Wiring Steps Figure 8...

Страница 8: ...and the white blue wire connected to pin 4 The drain wire should be connected to pin 4 along with the white blue wire Figure 10 1218CT Communication Module Board Postion Description Color 1 Data A Gre...

Страница 9: ...e GND terminal Position Color 1 Vo 5V Orange and White Orange 2 Vo Ground Brown and White Brown Description J1 Pin Assignments Figure 13 J1 Pin Assignments Table Configuration 1218 Console No configur...

Страница 10: ...Communication between the Communication Module and the FMS will be initiated by the FMS The FMS will send a command to the Communication Module then it will reply with data based on the command that...

Страница 11: ...he LEDs on the Communication Module if the Red LED is blinking this confirms there is a communication issue Refer to step 1 in this guide 2 If Red LED is not blinking check the wiring of the J3 connec...

Страница 12: ...g for the respective tank Starting date time and ending date time Starting volume and ending volume Starting height and ending height Note The 1218CT Communication Module will keep this log stored in...

Отзывы: