5
MORNINGSTAR
CORPORATION
1.3 Factory Settings
The Relay Driver is pre-configured at the factory with a default
configuration as outlined below. If a different configuration is
needed, a custom configuration will need to be programmed
into the Relay Driver.
Sections 2.0 through 5.0 explain software installation, custom
configuration, and installation.
Channel 1
Threshold Function:
Channel OFF when V
battery
< 11.5V
Channel ON when V
battery
> 12.6V
1 minute delay before turning on/off
Channel 2
Threshold Function:
Channel OFF when V
battery
< 11.1V
Channel ON when V
battery
> 12.2V
1 minute delay before turning on/off
Channel 3
Threshold Function:
Channel OFF when V
battery
< 14.0V
Channel ON when V
battery
> 15.0V
Channel 4
TriStar Alarm/Fault Monitor:
Channel OFF when no alarms/faults exist
Channel ON when any alarms/faults exist
Excludes RTS open alarm
No communication timeout alarm