Description of functioning
t e c h n i c a l
26
- Step 3.
Maximum DHW Power Regulation. Display shows P3 and electrical
value. Limited between 56 and 99.
- Light button: When pressed, display shows D.H.W. Temperature and electrical value
of this step.
- D.H.W. set point increase/decrease button: To set the electrical value.
- Winter Button (Central Heating): Push to store
th
e selected value
- Step 4.
Maximum DHW Power Regulation. Display shows P4 and electrical value.
To adjust this value use the same instructions that are used in Step 3.Limited between
20 and 55.
- Step 5.
Start-up Pressure Regulation. Display shows P5 and electrical value.
To adjust this value use the same instructions that are used in Step 3.Limited between
20 and 60.
- Step 6.
Check the boiler operation, sets the DHW temperature to 42ºC.
Display shows P6. No action possible in this step. Pushing light button, DHW tempe-
rature and hundred percent value of the gas valve are shown.
- Step 7.
Regulation of maximum heating Power and regulation at 85ºC. Display
shows P7 and electrical value. To adjust this value use the same instructions that are
used in Step 3.Limited between 20 and 99 for radiators and between 20 and 70 for
fl oor heating. Pushing UNLOCK button the fault memory will be cleared.