Electrical Connections

All electrical connections are made to terminals on
the front of the unit.  Each terminal is labeled.
Refer to the Installation drawings for connections.

To make a connection, loosen the screw that
corresponds to the terminal, install #6 ring or spade
lug on all wires and tighten the screw until snug or 8
inch pounds maximum.

Recommended Ground Wiring
Practices

The following ground wiring practices must be followed
to ensure proper performance of the FCT [UB]:

• Any Moore Industries product in a metal case

or housing should be grounded.

• All signals to and from Moore Industries’

products should be wired using a shielded,
twisted pair technique.  Shields are to be
connected to an earth or safety ground at the
unit.

• The maximum length of any unshielded input

and/or output signal wiring is 2 inches.

Operation

Once properly calibrated, connected, and powered,
the FCT [UB] will operate reliably for an extended
period of time.  Unit maintenance is a simple check
of terminal connections every six months.
If an FCT [UB] begins to malfunction or to function
below rated specifications, complete the following
checklist before calling the factory for assistance.

• Verify that all electrical connections are clean

and tight.

• Verify that the power source for the unit is

supplying power at levels rated safe and
appropriate according to product
specifications.

• Check the calibration of the instruments used

in calibrating the FCT [UB].

• Verify  that other devices in the process loop

are not the cause of the problem.

If the difficulties continue, remove the unit
from service and recalibrate.

Customer Support

Moore Industries is recognized as the industry
leader in delivering top quality to its customer, both
in products and services.  We perform a battery of
stringent quality asurance checks on every unit we
ship.  If any Moore Industries product fails to
perform up to rated specifications, call us for help.
Our highly skilled staff of trained technicians and
engineers pride themselves on their ability to
provide timely, accurate, and practical answers to
your process instrumentation questions.  Factory
phone numbers are on the back cover.

If problems involve a particular FCT [UB], there are
several pieces of information you can gather 

before

you call the factory that will help our staff to get
your  answers more efficiently.  When you call,
please have:

• The model number of the unit in question.
• The serial number of the unit in question.
• The job number (if available).
• The purchase order under which the unit

was shipped (if available).

Содержание FCT [UB]

Страница 1: ...FCT UB Page 1 The Interface Solution Experts FCT FCT UB Signal Converter Isolator April 2016 146 715 00 B Signal Converter Isolator UB SPAN ZERO FCTSIGNAL CONVERTER ISOLATOR...

Страница 2: ...Page 2 FCT UB The Interface Solution Experts Table of Contents Introduction 3 Description 3 Specifications 4 OrderingInformation 4 Calibration 5 6 Installation 7 9 Operation 8 Customer Support 8...

Страница 3: ...voiding minor inconveniences during calibration installation or operation A Caution provides information on steps to take to avoid procedures and practices that could risk damage to the FCT UB or othe...

Страница 4: ...eters Span 10 Zero 5 300 grams 0 6 lbs Performance continued Adjustments Ordering Information Input Output Unit FCT UB 0 20mA into 50 ohms 4 20mA into 50 ohms 0 50mA into 20 ohms 10 50mA into 20 ohms...

Страница 5: ...rather than in the field Use a technician s bench or a similar lab type environment Table 1 Calibration Equipment Equipment Specifications Voltage or Current Source Power Source Multimeter Ammeter or...

Страница 6: ...erclockwise minimum zero and span 15 turns then approximately 7 turns clockwise This approximates mid scale for the pots 2 Set the input source in the setup to 0 zero percent 1V for example if the FCT...

Страница 7: ...the FCT UB Moore Industries suggests that the calibration procedures be carried out to confirm that the configuration of the unit is appropriate for the intended application Costly down time will resu...

Страница 8: ...he factory for assistance Verify that all electrical connections are clean and tight Verify that the power source for the unit is supplying power at levels rated safe and appropriate according to prod...

Страница 9: ...ng the FCT UB Figure 3 Installing the FCT UB with the TX option SPAN ZERO RECEIVER VOLTAGE OR VOLTAGE TRANSMITTER VDC OR VAC POWER SOURCE IN IN OUT OUT GND PWR PWR SPAN ZERO RECEIVER 2 WIRE TRANSMITTE...

Страница 10: ...R BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT B...

Отзывы: