www.miinet.com
Moore Industries-International, Inc.
- 18 -
User’s Manual
238-741-00K
May 2019
Moore industries-International, Inc.
1. From the Online menu select “Device setup”.
2. Select “Custom Calibration”.
3. Select “AO Trim” (this allows you to trim the Analog Output)
4. Start with the “Trim Zero” function.
5. Follow and heed the information and instructions on the screen of your HART
Communicator.
6. Use your voltmeter to measure the voltage drop across the 250Ω resistor. A 4mA output
will read as 1V across the resistor.
7. Follow the instructions on the screen of your HART Communicator and then proceed to
“Trim Full”.
8. Use your voltmeter to measure the voltage drop across the 250Ω resistor. A 20mA output
will read as 5V across the resistor.
Figure 2.6.
Output Trimming with HART Communicator
Online Menu
Model
Device Setup
PV is
PV Quality
PV
PV Loop Current
PV LRV
PV URV
SV
TV
QV
Range Alarm
Status*
Process
Variables
Setup
Custom
Calibraon
Review
Status
Reset Trim
Input (PV) Capture
Trim Zero
Variable Trim
Trim Full
AO Trim
AO Trim Reset
Loop Test