www.miinet.com
Moore Industries-International, Inc.
- 49 -
User’s Manual
238-741-00K
May 2019
Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
SECTION 4
Read Additional Device status every 0.5 second if there are any status changes or every
hour if there are no status changes
HART command 48: Read Additional Device Status
Update period: 0.5 seconds;
Maximum update period: 3600 seconds
Trigger Mode: Change
Trigger Level: 1.0
Trigger Units: (250) Not Used
Sensor Diagnostics
Sensor Drift Alert using Range Alarms and Sensor Corrosion Detection can also be used for
predictive diagnostics to warn of future problems.
Broken Wire Holdoff Time allows you to add an additional time delay before a sensor broken
wire is reported which provides some noise immunity and prevents false alarms caused by other
factors that may be misinterpreted as Broken Wire.
Please refer to Section 1 for more detailed information on Sensor Diagnostics.
Input Quality Alarms
The THZ
3
/TDZ
3
also allows the user to determine how certain types of input quality issues are
handled and how they can affect the Device Variables, Dynamic Variables and AO. There are
3 different quality alarms: Measurement out of Conformance Range, Allow Limited and Allow
Dropping. See Section 6 for more information.