Programmable Limit Alarm Trips
SPA
2
SECTION 1
ENTER
PASS
Enter the password
code to enable
settings changes.
(Default = 55)
Scale Input "Smart Scaling":
Set the values to be displayed
at zero and full scale without
calibration equipment.
Trim Analog Output:
Connect the SPA
2
into a calibration
set-up as shown in the manual and
trim the analog output.
(Requires -AO Option)
Configure Input:
Select volt or current input.
Defaults to mA.
Password:
View or change password.
Apply Input (Bench Scaling):
Using calibration equipment,
capture the zero and full scale
values.
System Information:
View information such as
serial number, Firmware Version,
Hardware Version, Input Model,
and Output Model
Configure Options:
Set engineering units, decimal
places, 50/60Hz filter, broken wire
detection and scaling.
Security Jumper
installed in OFF position.
Security Jumper
installed in ON position.
Front Panel
Pushbuttons
Use the UP and DOWN pushbuttons
to scroll through menus and sub-menus.
Use the SELECT pushbutton to access
menus and/or make a choice.
CONFG
INPUT
CONFG
OPTNS
SCALE
INPUT
APPLY
INPUT
TRIM
AOUT
SYS
INFO
CONFG
ALARM
Configure Alarm:
Configure alarm types & settings.
CONFG
PASWD
TRIM
INPUT
Trim Input:
Match the actual reading of your
SPA
2
to a calibrated or known
value.
CONFG
AOUT
Scale Analog Output:
Connect the SPA
2
into a calibration
set-up as shown in the manual
and scale the analog output.
(Requires -AO Option)
SCALE
AOUT
SELECT
DOWN
UP
D
D
D
D
D
D
D
D
D
D
U
U
U
U
U
U
U
U
U
U
Exit Configuration Menu:
Return to process display.
CONFG
EXIT
D
D
U
Configure Analog Output:
Choose damping value and fail mode.
(Requires -AO Option)
SPA
2
HLPRG Quickstart Guide
Use the front push-buttons to quickly and easily
setup the SPA
2
for your application. After
programming your alarm using the diagram below,
install the unit into your application using the
connection diagram and terminal designation table
located in this manual.
Default/Factory Configuration
The following are the default factory settings for
your unit.
Input mA, 4-20mA
Display Normal Mode, PV
60Hz Filter
Broken wire enabled, level set to 0.1
Running Average Filter set to 4
All alarms set to Trip High at 12mA with Deadband set to 0
All alarms range set to 4-20mA
All alarms have OOR & Input Failure disabled
All alarms are configured as Fail Safe, latching disabled, 0 delay
AO (if fitted) : Current 4-20mA, fail high, hold duration of 1 second