The Interface Solution Experts 13
SPA
2
Programmable Current/Voltage
Limit Alarm Trips
Configuring the Input
Figure 6 gives an overview of the Input Configuration
menu.
If the Password Jumper is not installed, the password
sub-menu is bypassed, and the “CONFG INPUT”
menu is accessed by pressing
SELECT from the
process variable display.
1.
From the “CONFG INPUT” display, press
SELECT.
2.
At “INPUT TYPE” press
SELECT. The display
shows, “CURNT” or “VOLTS” (current or
voltage parameter). Use the
UP or DOWN
arrow buttons to scroll through the two options
for input type. The default display for this
menu is always the last setting.
3.
When the display shows the type of input,
current or voltage, that you choose to use,
press
SELECT.
4.
Next, the available input values are displayed.
Use the
UP or DOWN buttons to scroll through
the selections, choose a value that is greater
than or equal to the maximum value for the
input you will be monitoring and press
SELECT
when the value has been displayed.
5.
“EXIT INPUT” appears. If all values in this
parameter have been set, press
SELECT. If
not, return to the menu and set your values.
6.
The next display is the menu for the selection
of functional options, ”CONFG OPTNS”. To
skip the rest of the configuration menus and
return to the process variable display, press
the
UP button twice (to “CONFG EXIT”), and
press
SELECT.
Figure 6.
CONFG INPUT Menu
SEL
SEL
SEL
TOGGLE
CURRENT/
VOLTS
CONFG
INPUT
INPUT
TYPE
D
U
EXIT
INPUT
U
D
Volt List:
10V
5V
2.5V
1.25V
Current List:
50mA
25mA
12.5mA
6.25mA
CONFG OPTNS menu
SEL
SEL
SEL
Use the
UP and
Down buttons
to cycle through
the lists