 7

TRUNKGUARD™ 

Series Fieldbus Device Couplers

(Zone 1 Locations)

TG300

may be made only while the trunk is de-energized 
or under normal Zone 1 working practices (typically, 
under local supervision by gas detectors, etc). Spur 
connections can be made while the TG300 unit is 
energized only if the DISCONN Key is activated 
and only the YELLOW LED is ON for that spur. 
Alternatively, the whole segment should be de-
energized.

If the GREEN LED is ON at the same time as the 
YELLOW LED is ON, the segment has not been  
de-energized and no wiring work is permitted 
without removing power to that segment. If the RED 
LED is ON, then follow the steps in the 

Testing and 

Troubleshooting

 section.

Field devices should be certified/approved for use 
in hazardous areas (e.g. EEx d in Zone 1) and 
are typically connected using armored, braided or 
toughened-sheath cabling.  MooreHawke cable glands 
are EEx d and EEx e approved, but need to be sized 
for the appropriate armored or toughened cable.  
Earth continuity plates are provided, bonded to an 
external earth stud.

DISCONN Key

The DISCONN Key contains the magnet used 
to operate the magnetic interlock which permits 
individual fieldbus devices to be de-energized and 
worked on without de-powering the entire segment.  
You must have the DISCONN Key fully inserted into 
the spur receptacle for the spur to be de-energized. 

Recommended Ground Wiring 
Practices 

Moore Industries recommends the following ground 

wiring practices: 

• Any MooreHawke product in a metal case or 

housing should be grounded.

• The protective earth conductor must be 

connected to a system safety earth ground 

before making any other connections.

• The maximum length of unshielded input and 

output signal wiring should be 2 inches.

• Some local electrical codes or facility 

practices may require the Shield to be 

connected to Ground at more than one 
location.  Follow proper local guidelines.

Fieldbus segment cable Shields for spurs and 
trunks are gathered together in the device coupler 
and then wired through the trunk cable to the next 
device coupler and eventually to the fieldbus power 
conditioner.  Single point Grounding is recommended 
for segment shields.  Grounding of the segment shield 
usually occurs at the power conditioner.

Содержание Hawke TRUNKGUARD Series

Страница 1: ...TG300 TG300 May 2016 920091D TRUNKGUARD Series Fieldbus Device Couplers Zone 1 Locations TRUNKGUARD Series Fieldbus Device Couplers Zone 1 Locations...

Страница 2: ...oupler Enclosures 3 Specifications 4 Dimensions 4 Installation 6 Wiring Connections 6 Device Coupler Hook Up 6 DISCONN Key 7 Recommended Ground Wiring Practices 7 CE Conformity 8 Testing and Troublesh...

Страница 3: ...you see a Note Caution or WARNING pay particular attention WARNING Hazardous procedure or condition that could injure the operator Caution Hazardous procedure or condition that could damage or destro...

Страница 4: ...Internal Automatic Segment Termination is standard For manual Communications Performance termination specify the MT option with the MooreHawke model number e g TG308 DIN MT Also separately specify a T...

Страница 5: ...Enclosure Installation Dimensions 8 Spur Model 4 Spur Model OUT IN 1 2 3 4 250mm 9 85 in 200mm 7 87 in 120mm 4 72 in 255mm 10 04 in 235mm 9 25 in OUT IN 1 2 3 4 5 6 7 8 255mm 10 04 in 235mm 9 25 in 25...

Страница 6: ...e of installation Cables should be brought to the device coupler in such a way as to prevent external water from running into the cable entry position For cables coming vertically down to a device cou...

Страница 7: ...ded to an external earth stud DISCONN Key The DISCONN Key contains the magnet used to operate the magnetic interlock which permits individual fieldbus devices to be de energized and worked on without...

Страница 8: ...a core to shield fault on that spur cable Locate and repair any spur fault before reconnecting that spur All LEDs are OFF Any red LED is ON Table 1 LED Indications Testing and Troubleshooting Testing...

Страница 9: ...Customer Support If service assistance is ever required for an instrument in your application refer to the back cover of this manual for the telephone numbers to MooreHawke Customer Service Department...

Страница 10: ......

Страница 11: ...IES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO E...

Отзывы: